2-channel digital output; 24 VDC; Intrinsically safe.
The WAGO 750 series intrinsically-safe DC digital output slice module features 2 digital outputs (24Vdc, high-side switching, 2-wire) and operates with a supply voltage of 5Vdc provided by the system. It includes spring CAGE CLAMP connections, is designed for DIN-35 rail mounting with a 12mm width, and has an IP20 protection rating. The module is suitable for ambient temperatures ranging from 0°C to +55°C and is equivalent to model 750535.
- actuator connection:
- 2 x (2-wire)
- color:
- Blue
- conformity marking:
- CE
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.0416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- emc emission of interference:
- Per EN 61000-6-3, marine applications
- emc immunity to interference:
- Per EN 61000-6-2, marine applications
- ex guideline:
- EN IEC 60079-0, -7, -11
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 0.932 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- internal resistance ri:
- 285
- intrinsic safety ex i:
- Yes
- isolation:
- 300 VAC system/field
- load type:
- Resistive, inductive, lamp load
- marking:
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- note:
- The digital output module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
- number of digital outputs:
- 2
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- output characteristic:
- High-side switching
- output internal data width max:
- 2 bits
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 7 mA
- power consumption field supply module with no external load:
- 8.5 mA
- power consumption pmax:
- 2.1 W (at 40 mA output current)
- power loss pl:
- 1.1 W (at 40 mA output current)
- protection type:
- IP20
- reactances ex ia i:
- Lo = 20 mH: Co = 3.6 F
- reactances ex ia iia:
- Lo = 18 mH: Co = 2.2 F
- reactances ex ia iib:
- Lo = 12 mH: Co = 680 nF
- reactances ex ia iic:
- Lo = 3 mH: Co = 88 nF
- reactances note:
- Reactances without accounting for the concurrence of L and C
- relative humidity without condensation:
- 0.95
- safety relevant data circuit:
- Uo = 27.3 V: Io = 106 mA: Po = 723 mW: Linear characteristic curve
- shock resistance:
- 15g per IEC 60068-2-27
- signal type:
- Voltage
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- switching frequency max:
- 1 kHz
- total number of channels module:
- 2
- vibration resistance:
- 4g per IEC 60068-2-6
- voltage signal type:
- 24 VDC
- weight:
- 50.600 g
- width:
- 12 mm / 0.472 inch