- actuator connection:
- 2 x (2-wire)
- color:
- Blue
- conformity marking:
- CE
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- contact material:
- Ag alloy (with gold flash)
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.0416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- drop out time max:
- 4 ms
- electrical switching operations min at max resistive load:
- 1 x 105
- emc emission of interference:
- Per EN 61000-6-3, marine applications
- emc immunity to interference:
- Per EN 61000-6-2, marine applications
- ex guideline:
- EN IEC 60079-0, -7, -11
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 0.874 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- intrinsic safety ex i:
- Yes
- isolation:
- 300 VAC system/field
- load type:
- Resistive, inductive, lamp load
- marking:
- ATEX, IECEx, Underwriters Laboratories Inc.
- mechanical switching operations min at max resistive load:
- 100 x 106
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- note:
- The digital output module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
- number of digital outputs:
- 2
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- output characteristic:
- Potential-free
- output circuit design:
- 2 changeover contacts || Relays
- output internal data width max:
- 2 bits
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 26 mA
- power consumption field supply module with no external load:
- 24 mA
- power consumption pmax:
- 0.8 W
- power loss pl:
- 0.8 W
- protection type:
- IP20
- pull in time max:
- 4 ms
- relative humidity without condensation:
- 0.95
- safety relevant data circuit:
- Relay output: Ui = 30 VDC: Ii = 1 A: Pi = 30 W: Ui = 100 VAC: Ii = 0.5 A: Pi = 50 VA: Li = negligibly small: Ci = negligibly small
- shock resistance:
- 15g per IEC 60068-2-27
- signal type:
- Voltage
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- switching current max:
- 0.5 A
- switching current min:
- 0.01 mA
- switching current note:
- 0.5 A at 100 VAC: 1 A at 30 VDC
- switching frequency max:
- 0.3 Hz
- switching power:
- 50 VA / 30 W
- switching voltage max:
- 100 VAC, 30 VDC
- switching voltage min:
- 0.1 V
- total number of channels module:
- 2
- vibration resistance:
- 4g per IEC 60068-2-6
- voltage signal type:
- 100 VAC: 30 VDC
- weight:
- 49.100 g
- width:
- 12 mm / 0.472 inch