Yes, max. 3 battery modules for buffer time extension (temperature measurement evaluation is only possible via one battery module)
pollution degree:
2
power loss pl:
¤ 15 W (No load): ¤ 20 W (Nominal load)
protection class:
III
protection type:
IP20 (per EN 60529)
recommended battery module:
787-871, 787-872, 787-873, 787-876, 787-1671
relative humidity:
5 96 % (no condensation permissible)
remote input:
Switching buffer mode off
resistance to reverse feed:
¤ DC 35 V
reverse voltage protection:
Yes
series operation:
No
signaling:
1 x LED DC OK (green) || 1 x Warning LED (yellow) || 1 x Error LED (red) || LCD || 3 x Signal output (24 VDC: max. 25 mA) || 1 x Isolated relay contact (max. 30 VDC: 1 A) || 1 x RS-232 interface || Battery control (C+: C-)
solid conductor:
0.08 2.5 mm / 28 12 AWG
solid conductor 2:
0.08 0.5 mm / 28 20 AWG
standards specifications:
EN 61010-1 || EN 61010-2-201 || UL 60950 || UL 508 || EN 61000-6-2 || EN 61000-6-3
Switched-mode power supply with TopBoost, enabling secondary-side protection via circuit breakers Natural convection cooling when horizontally mounted ...