Schneider Electric

Schneider Electric 8911DPSG43V07 Starter, Definite Purpose, nonreversing, 40A, 3 pole, 3 phase, 600VAC coil, melting alloy overload, NEMA 1, +options

(No reviews yet) Write a Review
SKU:
8911DPSG43V07
MPN:
8911DPSG43V07
Condition:
New
Nema Degree Of Protection:
NEMA 1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Number Of Thermal Units Required:
3
Country of Origin:
Mexico
Enclosure Material:
painted sheet steel
Phase:
3 phase
Maximum Horse Power Rating:
3-3 hp 115 V AC, 1 phase || 10-10 hp 230 V AC, 3 phase || 7.5-7.5 hp 230 V AC, 1 phase || 20-20 hp 460 V AC, 3 phase || 25-25 hp 575 V AC, 3 phase
[Ue] Rated Operational Voltage:
600 V AC
Locked Rotor Rated Current:
240 A 230 V AC || 200 A 460 V AC || 160 A 575 V AC
Eu Rohs Directive:
Compliant with Exemptions
Rohs Exemption Information:
Yes
Warranty:
18 months
Thermal Overload Type:
melting alloy
Line Rated Current:
40 A
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Poles Description:
3P
[Uc] Control Circuit Voltage:
550 V AC 50 Hz || 600 V AC 60 Hz
Product Or Component Type:
Definite Purpose Starter
Range Of Product:
DPS
$496.44

Description

8911 definite purpose starters are inexpensive starters for applications with relatively low duty cycles. Typical applications include air compressors, agricultural equipment, pumps, and HVAC equipment. The starter comes nonreplaceable coil is available with a variety of coil voltages as well as auxillary contacts. All definite purpose starters hav melting alloy type overload relay uses Type B thermal units to sense over current conditions. This three pole definite purpose starter has a full load rating of 40 amperes. Starter is supplied with a 550/600 VAC 50/60 Hz coil This starter has ratings of 3 HP at 115 VAC and 7.5 HP at 230 VAC single phase. It has a rating of 10 HP at 230 VAC, 15 HP 460 VAC and 20 HP at 575 VAC poly phase. A painted sheet steel NEMA 1 general purpose enclosure is used to protect this definite purpose starter. 8911DPS definite purpose starters are UL component recognized.
View AllClose