Schneider Electric

Schneider Electric ATS22C32Q soft starter for asynchronous motor, Altistart 22, control 230V, 230 to 440V, 90 to 160kW

(No reviews yet) Write a Review
SKU:
ATS22C32Q
MPN:
ATS22C32Q
Condition:
New
Icl Starter Rating:
320 A connection in the motor supply line for standard applications
Ptc Probe Input:
750 Ohm
Height:
425 mm
Discrete Output Number:
2
China Rohs Regulation:
X
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Discrete Output Type:
relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O || relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Noise Level:
56 dB
Vibration Resistance:
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm 2-13 Hz)IEC 60068-2-6
Range Of Product:
Altistart 22
Rohs Exemption Information:
Yes
Relative Humidity:
0-95 % without condensation or dripping water IEC 60068-2-3
Assembly Style:
with heat sink
Device Connection:
to the motor delta terminals || in the motor supply line
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
Marking:
CE
Power Dissipation In W:
150 W for standard applications
Supply Frequency:
50...60 Hz - 10...10 %
Electromagnetic Compatibility:
conducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electr
Minimum Switching Current:
100 mA 12 V DC relay outputs)
Warranty:
18 months
Phase:
3 phase
Motor Starter Type:
soft starter
Control Circuit Consumption:
20 W
Discrete Input Logic:
positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
Type Of Cooling:
forced convection
Pollution Degree:
level 2 IEC 60664-1
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
[Uc] Control Circuit Voltage:
230 V - 15...10 % 50/60 Hz
Mercury Free:
Yes
Discrete Input Type:
LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Discrete Input Voltage:
24 V <= 30 V
Power Range:
55-100 kW 200-240 V 3 phase || 110-220 kW 380-440 V 3 phase
Communication Port Protocol:
Modbus
Output Current:
0.4...1 Icl adjustable
Physical Interface:
RS485 multidrop
Factory Setting Current:
285 A
Standards:
IEC 60947-4-2
Operating Position:
vertical +/- 10 degree
Motor Power Kw:
160 kW 400 V || 160 kW 440 V || 90 kW 230 V
Product Certifications:
UL || CCC || C-tick || CSA || GOST
Network Frequency:
45...66 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Function Available:
internal bypass
Maximum Switching Current:
5 A 250 V AC resistive 1 relay outputs || 5 A 30 V DC resistive 1 relay outputs || 2 A 250 V AC inductive 0.4 20 ms relay outputs || 2 A 30 V DC inductive 7 ms relay outputs
Product Destination:
asynchronous motors
Ambient Air Temperature For Operation:
-10-40°C without derating) || 40-60°C with current derating 2.2 % per°C)
Protection Type:
phase failure line || thermal protection motor || thermal protection starter
Depth:
299 mm
Ambient Air Temperature For Storage:
-25-70°C
$3,699.60

Description

This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 320A and 230V to 440V, a rated power up to 160kW (400V to 440V in supply line) and up to 250kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
View AllClose