Schneider Electric

Schneider Electric CAD50ED TeSys Deca control relay - 5 NO - <= 690 V - 48 V DC standard coil

(No reviews yet) Write a Review
SKU:
CAD50ED
MPN:
CAD50ED
Condition:
New
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Ip Degree Of Protection:
IP2X front face VDE 0106
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Product Name:
TeSys CAD
Weight:
0.58 kg
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Operating Altitude:
0...9842.52 ft (0...3000 m)
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Eu Rohs Directive:
Compliant with Exemptions
Environmental Disclosure:
ENVPEP110230EN
Country of Origin:
Mexico
Inrush Power In W:
5.4-5.4 W 20°C)
Circularity Profile:
ENVEOLI1102030EN
Range:
TeSys || TeSys Deca
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
control relay
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
Minimum Switching Current:
5 mA
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
Rohs Exemption Information:
Yes
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Minimum Switching Voltage:
17 V
Insulation Resistance:
> 10 MOhm
Mercury Free:
Yes
Ambient Air Temperature For Storage:
-60-80°C
Contactor Application:
control circuit
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
[Uc] Control Circuit Voltage:
48 V DC
Tightening Torque:
1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
Connections - Terminals:
screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || sc
Mechanical Durability:
30 Mcycles
Mounting Support:
plate || rail
Utilisation Category:
AC-14 || DC-13 || AC-15
Operating Time:
53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening
Maximum Operating Rate:
180 cyc/mn
Sustainable Offer Status:
Green Premium product
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Pole Contact Composition:
5 NO
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Net Weight:
0.58 kg
Depth:
93 mm
Time Constant:
28 ms
$112.20

Description

TeSys D control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 48V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose