- Mounting Support:
- rail || plate
- Ambient Air Temperature For Operation:
- -20-60°C
- 9 Mm Pitches:
- 2
- Ambient Air Temperature For Storage:
- -40-80°C
- Poles Description:
- 1P + N
- Control Type:
- toggle
- Warranty:
- 18 months
- Product Certifications:
- UL || CSA
- Reach Free Of Svhc:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV IEC 60947-2
- Utilisation Category:
- category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Product Or Component Type:
- circuit breaker
- Protective Treatment:
- TC
- Toxic Heavy Metal Free:
- Yes
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ue] Rated Operational Voltage:
- 250 V AC 50/60 Hz IEC 60947-2 || 277 V AC 60 Hz CSA C22.2 No 235 || 277 V AC 60 Hz UL 1077 || 48 V DC
- Ip Degree Of Protection:
- IP20 IEC 60529
- Line Rated Current:
- 0
- Environmental Disclosure:
- ENVPEP2306023
- Mechanical Durability:
- 8000 cycles
- Network Frequency:
- 50/60 Hz IEC 60947-2
- Mounting Mode:
- by clips
- Quantity Per Set:
- set of 6
- Device Short Name:
- GB2
- Depth:
- 67 mm
- Range:
- TeSys
- Net Weight:
- 0.07 kg
- Electrical Durability:
- 8000 cycles
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-2 || CSA C22.2 No 235 || UL 1077
- Weight:
- 0.07 kg
- [Ics] Rated Service Short-Circuit Breaking Capacity:
- 75 % 110 V AC 50/60 Hz IEC 60947-2 || 75 % 230/240 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Breaking Capacity:
- 2 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2
- Power Dissipation Per Pole:
- 2 W
- Operating Altitude:
- 9842.52 ft (3000 m)
- Country of Origin:
- France
- Circularity Profile:
- N/A
- Sustainable Offer Status:
- Green Premium product
- Mechanical Robustness:
- shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
- Fire Resistance:
- 960°C IEC 60695-2-1
- Network Type:
- AC/DC
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Mounting Position:
- vertical || horizontal
- Width:
- 15 mm
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant
- Tightening Torque:
- 1.2 N.m connector