Schneider Electric

Schneider Electric GB2DB07 TeSys GB2 thermal magnetic circuit protector, 2 P, 2 A, Id = 26 A

(No reviews yet) Write a Review
SKU:
GB2DB07
MPN:
GB2DB07
Condition:
New
Country of Origin:
France
Environmental Disclosure:
ENVPEP2306022
[Ue] Rated Operational Voltage:
415 V AC 50/60 Hz IEC 60947-2 || 48 V DC
[Uimp] Rated Impulse Withstand Voltage:
4 kV IEC 60947-2
Product Name:
TeSys GB2
Network Type:
AC/DC
Weight:
0.115 kg
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2
Electrical Durability:
8000 cycles
Tightening Torque:
1.2 N.m connector
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Type:
toggle
Device Application:
control
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Line Rated Current:
0.0833333333333333
Depth:
70 mm
Mechanical Robustness:
shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
Mounting Support:
rail || plate
Mounting Mode:
by clips
Ip Degree Of Protection:
IP20 IEC 60529
Poles Description:
2P
Eu Rohs Directive:
Compliant
Ambient Air Temperature For Storage:
-40-80°C
Circularity Profile:
N/A
Breaking Capacity:
15 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2 || 1 kA Icu 48 V DC IEC 60947-2
Operating Altitude:
9842.52 ft (3000 m)
Product Or Component Type:
circuit breaker
Mounting Position:
vertical || horizontal
9 Mm Pitches:
4
Magnetic Tripping Current:
26-26 A
Mercury Free:
Yes
Range:
TeSys
Reach Free Of Svhc:
Yes
Device Short Name:
GB2
Net Weight:
0.115 kg
Ambient Air Temperature For Operation:
-20-60°C
Toxic Heavy Metal Free:
Yes
Connections - Terminals:
connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Power Dissipation Per Pole:
2 W
Trip Unit Technology:
thermal-magnetic
Warranty:
18 months
Mechanical Durability:
8000 cycles
Utilisation Category:
category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
$93.00

Description

TeSys GB circuit breaker, 2 poles (2P), 2A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 26A (13 In) and breaking capacity Icu 15kA@415V. It can also be used for protection of DC loads up to 2A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2, Green Premium product (RoHS/REACh).
View AllClose