Schneider Electric

Schneider Electric GV4P80B6 Motor circuit breaker, TeSys GV4, 3P, 80A, Icu 25kA, thermal magnetic, lugs terminals

(No reviews yet) Write a Review
SKU:
GV4P80B6
MPN:
GV4P80B6
Condition:
New
Ambient Air Temperature For Operation:
-25-70°C
Electrical Durability:
14000 cycles AC-3 440 V In/2 || 7000 cycles AC-3 440 V In
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Net Weight:
1.6 kg
Halogen Content Performance:
Halogen free plastic parts product
Motor Power Kw:
37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 22-22 kW 400...415 V AC 50/60 Hz || 30-30 kW 500 V AC 50/60 Hz || 37-37 kW 660...690 V AC 50/60 Hz || 45-45 kW 660...690 V AC 50/60 Hz || 55-55 kW 660...690 V AC 50/60 Hz || 30-30 kW 4
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology:
thermal-magnetic || electronic
Phase Failure Sensitivity:
yes IEC 60947-4-1
Fire Resistance:
960°C IEC 60695-2-11
Weight:
1.6 kg
Product Or Component Type:
motor circuit breaker
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Mechanical Durability:
40000 cycles
Rohs Exemption Information:
Yes
Connection Pitch:
27 mm without spreaders || 35 mm with spreaders
Maximum Operating Rate:
25 cyc/h
Circularity Profile:
ENVEOLI1704004EN
Mercury Free:
Yes
Range Of Product:
TeSys GV4
Control Type:
rotary handle
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Suitability For Isolation:
yes IEC 60947-1
Country of Origin:
Poland
Rated Duty:
continuous IEC 60947-4-1
Warranty:
18 months
Ambient Air Temperature For Storage:
-50-85°C
Ik Degree Of Protection:
IK07 IEC 62262
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Sustainable Offer Status:
Green Premium product
Line Rated Current:
80 A
Magnetic Tripping Current:
1360-1360 A
Color:
Gray RAL 7016)
Environmental Disclosure:
ENVPEP1704004EN
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Device Short Name:
GV4P
Ip Degree Of Protection:
IP40 IEC 60529
Device Application:
motor protection
Eu Rohs Directive:
Compliant with Exemptions
Breaking Capacity:
50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 35 kA 208Y/120 V AC 50/60 Hz UL 60947 || 35 kA 240 V AC 50/60 Hz U
Depth:
165 mm
Pvc Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Poles Description:
3P
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
$1,117.50

Description

TeSys GV motor circuit breaker, 3 poles (3P), 80A/690V, for protection of 3-phase motors 22-37kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by rotary handle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 40-80A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).