Schneider Electric GV4PE02N Motor circuit breaker, TeSys GV4, 3P, 2A, Icu 50kA, thermal magnetic, Everlink terminals
Schneider Electric
$695.00
TeSys GV motor circuit breaker, 3 poles (3P), 2A/690V, for protection of 3-phase motors 0.25-0.75kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 0.8-2A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
- Rated Duty:
- continuous IEC 60947-4-1
- Warranty:
- 18 months
- Operating Position:
- any position
- Electrical Durability:
- 40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
- Country of Origin:
- Poland
- Height:
- 155 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Phase Failure Sensitivity:
- yes IEC 60947-4-1
- Range Of Product:
- TeSys GV4
- Ambient Air Temperature For Operation:
- -25-70°C
- Environmental Disclosure:
- ENVPEP1704004EN
- Operating Altitude:
- 5000 m
- Ambient Air Temperature For Storage:
- -50-85°C
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- motor circuit breaker
- Connections - Terminals:
- EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
- Ip Degree Of Protection:
- IP40 IEC 60529
- Power Dissipation Per Pole:
- 4.6 W
- Weight:
- 1.45 kg
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pvc Free:
- Yes
- Ik Degree Of Protection:
- IK07 IEC 62262
- Product Certifications:
- IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity:
- 100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz
- Maximum Operating Rate:
- 25 cyc/h
- Mercury Free:
- Yes
- Device Application:
- motor protection
- Pollution Degree:
- 3
- Color:
- Gray RAL 7016)
- Motor Power Kw:
- 0.25-0.25 kW 400...415 V AC 50/60 Hz || 0.37-0.37 kW 400...415 V AC 50/60 Hz || 0.55-0.55 kW 400...415 V AC 50/60 Hz || 0.75-0.75 kW 400...415 V AC 50/60 Hz || 0.37-0.37 kW 500 V AC 50/60 Hz || 0.55-0.55 kW 500 V AC 50/60 Hz || 0.75-0.75 kW 500 V AC
- Tightening Torque:
- 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
- Halogen Content Performance:
- Halogen free plastic parts product
- Mechanical Durability:
- 40000 cycles
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Fire Resistance:
- 960°C IEC 60695-2-11
- Depth:
- 116 mm
- Range:
- TeSys Deca
- Mechanical Robustness:
- vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
- Standards:
- CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
- [Ith] Conventional Free Air Thermal Current:
- 115 A IEC 60947-4-1
- Climatic Withstand:
- IACS E10
- Control Type:
- toggle
- Circularity Profile:
- ENVEOLI1704004EN
- Net Weight:
- 1.45 kg
- Device Short Name:
- GV4PE