Schneider Electric LC1D096B7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VAC 50/60Hz coil, open style
Schneider Electric
$112.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Connections - Terminals:
- control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Utilisation Category:
- AC-4 || AC-1 || AC-3 || AC-3e
- Depth:
- 86 mm
- [Uc] Control Circuit Voltage:
- 24 V AC 50/60 Hz
- Pollution Degree:
- 3
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Device Short Name:
- LC1D
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Signaling Circuit Frequency:
- 25...400 Hz
- Protective Treatment:
- THIEC 60068-2-30
- Environmental Disclosure:
- ENVPEP1501004
- Toxic Heavy Metal Free:
- Yes
- Contactor Application:
- motor control || resistive load
- Pole Contact Composition:
- 3 NO
- Pvc Free:
- Yes
- Mounting Support:
- plate || rail
- Product Certifications:
- GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
- Fire Resistance:
- 850°C IEC 60695-2-1
- Rohs Exemption Information:
- Yes
- Flame Retardance:
- V1 conforming to UL 94
- Coil Technology:
- without built-in suppressor module
- Eu Rohs Directive:
- Compliant
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Circularity Profile:
- ENVEOLI1501004
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Sustainable Offer Status:
- Green Premium product
- Weight:
- 0.32 kg
- Protective Cover:
- with
- [Ith] Conventional Free Air Thermal Current:
- 25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
- Mechanical Durability:
- 15 Mcycles
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Motor Power Kw:
- 2.2 kW at 220...230 V AC 50/60 Hz (AC-3) || 4 kW at 380...400 V AC 50/60 Hz (AC-3) || 4 kW at 415 V AC 50/60 Hz (AC-3) || 4 kW at 440 V AC 50/60 Hz (AC-3) || 5.5 kW at 500 V AC 50/60 Hz (AC-3) || 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 2.2 kW at
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Overvoltage Category:
- III
- Tightening Torque:
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3