Schneider Electric

Schneider Electric LC1D256L7 IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, 3 phase, 3 pole, 3 NO, 200VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D256L7
MPN:
LC1D256L7
Condition:
New
Circularity Profile:
ENVEOLI110229EN
Coil Technology:
without built-in suppressor module
Operating Time:
12...22 ms closing || 4...19 ms opening
Mechanical Durability:
15 Mcycles
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Heat Dissipation:
2-3 W at 50/60 Hz
Pole Contact Composition:
3 NO
Mounting Support:
rail || plate
Insulation Resistance:
> 10 MOhm for Signaling circuit
Minimum Switching Current:
5 mA for Signaling circuit
Environmental Disclosure:
ENVPEP110229EN
Signaling Circuit Frequency:
25...400 Hz
Toxic Heavy Metal Free:
Yes
Contactor Application:
resistive load || motor control
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Power Dissipation Per Pole:
3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
Sustainable Offer Status:
Green Premium product
Warranty:
18 months
Overvoltage Category:
III
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Country of Origin:
France
Mercury Free:
Yes
Product Or Component Type:
contactor
Depth:
92 mm
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Motor Power Kw:
5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Device Short Name:
LC1D
Protective Cover:
with
Electrical Durability:
1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Control Circuit Type:
AC 50/60 Hz
California Proposition 65:
WARNING: Cancer - www.P65Warnings.ca.gov
Rohs Exemption Information:
Yes
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Fire Resistance:
850°C IEC 60695-2-1
Maximum Operating Rate:
3600 cyc/h 60°C
Weight:
0.37 kg
Eu Rohs Directive:
Compliant
$181.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 200 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose