Schneider Electric LC1D258G7 IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D258G7
MPN:
LC1D258G7
Condition:
New
Width:
45 mm
Overvoltage Category:
III
Flame Retardance:
V1 conforming to UL 94
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Fire Resistance:
850°C IEC 60695-2-1
Operating Time:
12...22 ms closing || 4...19 ms opening
Circularity Profile:
ENVEOLI110229EN
[Ie] Rated Operational Current:
40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Operating Altitude:
0...9842.52 ft (0...3000 m)
Sustainable Offer Status:
Green Premium product
Country of Origin:
Indonesia
Device Short Name:
LC1D
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Product Certifications:
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Pollution Degree:
3
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Weight:
0.425 kg
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Mounting Support:
rail || plate
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Pvc Free:
Yes
Height:
91 mm
Minimum Switching Current:
5 mA for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Range Of Product:
TeSys Deca
Eu Rohs Directive:
Compliant
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Power Dissipation Per Pole:
3.2 W AC-1
Depth:
99 mm
Pole Contact Composition:
2 NO + 2 NC
Electrical Durability:
1.4 Mcycles 40 A AC-1 <= 440 V
Heat Dissipation:
2-3 W at 50/60 Hz
Compatibility Code:
LC1D
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Circuit Type:
AC 50/60 Hz
Warranty:
18 months
Insulation Resistance:
> 10 MOhm for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.8 N.m screw clamps terminals flat Ø 6 mm || po
Protective Treatment:
THIEC 60068-2-30
Ip Degree Of Protection:
IP20 front face IEC 60529
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
$246.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.