Schneider Electric

Schneider Electric LC1D32GD IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 125VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D32GD
MPN:
LC1D32GD
Condition:
New
Time Constant:
28 ms
Pvc Free:
Yes
Fire Resistance:
850°C IEC 60695-2-1
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Mounting Support:
plate || rail
Mechanical Durability:
30 Mcycles
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Pollution Degree:
3
Contactor Application:
resistive load || motor control
Operating Altitude:
0...9842.52 ft (0...3000 m)
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Inrush Power In W:
5.4-5.4 W 20°C)
Compatibility Code:
LC1D
Product Or Component Type:
contactor
Signaling Circuit Frequency:
25...400 Hz
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Sustainable Offer Status:
Green Premium product
Overvoltage Category:
III
Country of Origin:
France
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Insulation Resistance:
> 10 MOhm for Signaling circuit
Protective Treatment:
THIEC 60068-2-30
Eu Rohs Directive:
Compliant with Exemptions
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Range Of Product:
TeSys Deca
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Device Short Name:
LC1D
Net Weight:
0.535 kg
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Circularity Profile:
ENVEOLI1102030EN
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Control Circuit Type:
DC standard
Minimum Switching Voltage:
17 V for Signaling circuit
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Flame Retardance:
V1 conforming to UL 94
Rohs Exemption Information:
Yes
Protective Cover:
with
Depth:
101 mm
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Warranty:
18 months
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Maximum Operating Rate:
3600 cyc/h 60°C
[Uc] Control Circuit Voltage:
125 V DC
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Ip Degree Of Protection:
IP20 front face IEC 60529
$215.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose