Schneider Electric

Schneider Electric LC1D40ALE7 IEC contactor, TeSys Deca, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 208VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D40ALE7
MPN:
LC1D40ALE7
Condition:
New
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
Electrical Durability:
1.4 Mcycles 60 A AC-1 <= 440 V || 1.5 Mcycles 40 A AC-3 <= 440 V || 1.5 Mcycles 40 A AC-3e <= 440 V
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 60 A (at 60°C) for power circuit
Mechanical Durability:
6 Mcycles
Protective Treatment:
THIEC 60068-2-30
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Weight:
0.85 kg
Reach Free Of Svhc:
Yes
Control Circuit Type:
AC 60 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Toxic Heavy Metal Free:
Yes
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Operating Time:
4...19 ms opening || 12...26 ms closing
Ip Degree Of Protection:
IP20 front face IEC 60529
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Pvc Free:
Yes
Pole Contact Composition:
3 NO
Average Impedance:
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Height:
122 mm
Mercury Free:
Yes
Range:
TeSys || TeSys Deca
Range Of Product:
TeSys Deca
Circularity Profile:
ENVEOLI1503009EN
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Motor Power Kw:
18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 415...440 V AC 50/60 Hz (AC-3) || 22 kW at 500 V AC 50/60 Hz (AC-3) || 30 kW at 660...690 V AC 50/60 Hz (AC-3) || 9 kW at 400 V AC 50/60 Hz (AC-4) || 18.
Power Dissipation Per Pole:
2.4 W AC-3 || 5.4 W AC-1 || 2.4 W AC-3e
Maximum Operating Rate:
3600 cyc/h 60°C
Rohs Exemption Information:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C)
Eu Rohs Directive:
Compliant
Protective Cover:
with
[Icw] Rated Short-Time Withstand Current:
320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Contactor Application:
resistive load || motor control
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight:
0.85 kg
Poles Description:
3P
Product Or Component Type:
contactor
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C)
Heat Dissipation:
4-5 W at 60 Hz
$261.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 208 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose