Schneider Electric

Schneider Electric LC1D40M7 IEC contactor, TeSys D, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D40M7
MPN:
LC1D40M7
Condition:
New
Power Dissipation Per Pole:
5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
Coil Technology:
without built-in bidirectional peak limiting diode suppressor
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Utilisation Category:
AC-1 || AC-4 || AC-2 || AC-3 || AC-3e
Contactor Application:
motor control || resistive load
Minimum Switching Voltage:
17 V for control circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Product Or Component Type:
contactor
Terminals Description Iso N°1:
(21-22)NC || (13-14)NO || (A1-A2)CO
Net Weight:
1.4 kg
Sustainable Offer Status:
Green Premium product
Mercury Free:
Yes
Depth:
119 mm
[Uc] Control Circuit Voltage:
220 V AC 50/60 Hz
Protective Cover:
with
[Ie] Rated Operational Current:
40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Associated Fuse Rating:
10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Environmental Disclosure:
ENVPEP110205EN
Country of Origin:
Czechia
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Fire Resistance:
850°C IEC 60695-2-1
Flame Retardance:
V1 conforming to UL 94
Weight:
1.4 kg
[Ui] Rated Insulation Voltage:
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
Toxic Heavy Metal Free:
Yes
Compatibility Code:
LC1D
Eu Rohs Directive:
Compliant
Operating Time:
4...19 ms opening || 12...26 ms closing
Insulation Resistance:
> 10 MOhm for control circuit
Height:
127 mm
Mounting Support:
plate || rail
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable en
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Mechanical Durability:
6000000 cycles
Heat Dissipation:
4-5 W at 50/60 Hz for control circuit
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Maximum Horse Power Rating:
3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp
Auxiliary Contact Composition:
1 NO + 1 NC
Pvc Free:
Yes
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for control circuit || 60 A (at 60°C) for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Overvoltage Category:
III
Climatic Withstand:
IACS E10 exposure to damp heat
Circularity Profile:
N/A
$361.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.