Schneider Electric

Schneider Electric LC1D50ABNE IEC contactor, TeSys Deca Green, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil, open

(No reviews yet) Write a Review
SKU:
LC1D50ABNE
MPN:
LC1D50ABNE
Condition:
New
Signaling Circuit Frequency:
25...400 Hz
Motor Power Kw:
15 kW at 220...230 V AC 50 Hz (AC-3) || 22 kW at 380...400 V AC 50 Hz (AC-3) || 25 kW at 415 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3) || 30 kW at 500 V AC 50 Hz (AC-3) || 33 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 220...230 V AC 50 H
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
Minimum Switching Current:
5 mA for Signaling circuit
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Operating Time:
55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
Protective Cover:
with
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Rohs Exemption Information:
Yes
Environmental Disclosure:
ENVPEP1607010EN
Halogen Content Performance:
Halogen free plastic parts & cables product
Operating Altitude:
0...9842.52 ft (0...3000 m)
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Pole Contact Composition:
3 NO
Mechanical Durability:
6 Mcycles
Hold-In Power Consumption In W:
0.7-0.7 W 20°C
Width:
55 mm
Height:
122 mm
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity Profile:
ENVEOLI1607010EN
Maximum Horse Power Rating:
3 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors || 15 hp at 200/208 V AC 60 Hz for 3 phase motors || 15 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 40 h
Mounting Support:
rail || plate
Overvoltage Category:
III
Product Or Component Type:
contactor
Heat Dissipation:
0.7-0.7 W at 50/60 Hz
Power Dissipation Per Pole:
9.6 W AC-1 || 3.7 W AC-3 || 3.7 W AC-3e
Depth:
120 mm
Poles Description:
3P
Control Circuit Type:
AC/DC 50/60 Hz AC/DC electronic
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Mercury Free:
Yes
Device Short Name:
LC1D
Net Weight:
0.997 kg
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 400 A 40°C - 10 s for power circuit || 810 A 40°C - 1
Minimum Switching Voltage:
17 V for Signaling circuit
Fire Resistance:
850°C IEC 60695-2-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Coil Technology:
built-in bidirectional peak limiting
Irms Rated Making Capacity:
900 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Sustainable Offer Status:
Green Premium product
Insulation Resistance:
> 10 MOhm for Signaling circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Flame Retardance:
V1 conforming to UL 94
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC-3e for power circuit
$129.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose