Schneider Electric

Schneider Electric LC1D50AEHE IEC contactor, TeSys Deca Green, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48/130VAC/VDC coil

(No reviews yet) Write a Review
SKU:
LC1D50AEHE
MPN:
LC1D50AEHE
Condition:
New
Hold-In Power Consumption In Va:
1.4-1.4 VA 50/60 Hz (at 20°C)
Country of Origin:
France
Circularity Profile:
ENVEOLI1607010EN
Depth:
120 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Short Name:
LC1D
Inrush Power In W:
19-19 W 20°C)
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
Range Of Product:
TeSys Deca
Height:
122 mm
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Minimum Switching Voltage:
17 V for Signaling circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Environmental Disclosure:
ENVPEP1607010EN
Overvoltage Category:
III
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC-3e for power circuit
Operating Time:
55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Flame Retardance:
V1 conforming to UL 94
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Utilisation Category:
AC-1 || AC-3 || AC-3e
Electrical Durability:
1.8 Mcycles 42 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.8 Mcycles 42 A AC-3e <= 440 V
Net Weight:
0.997 kg
Halogen Content Performance:
Halogen free plastic parts & cables product
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Coil Technology:
built-in bidirectional peak limiting
Mounting Support:
rail || plate
Ip Degree Of Protection:
IP20 front face IEC 60529
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Pollution Degree:
3
Range:
TeSys || TeSys Deca
Protective Cover:
with
Weight:
0.997 kg
Motor Power Kw:
15 kW at 220...230 V AC 50 Hz (AC-3) || 22 kW at 380...400 V AC 50 Hz (AC-3) || 25 kW at 415 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3) || 30 kW at 500 V AC 50 Hz (AC-3) || 33 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 220...230 V AC 50 H
Control Circuit Type:
AC/DC 50/60 Hz AC/DC electronic
Contactor Application:
resistive load || motor control
[Ith] Conventional Free Air Thermal Current:
80 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms Rated Making Capacity:
900 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Heat Dissipation:
0.9-0.9 W at 50/60 Hz
$129.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose