Schneider Electric LC1D65004G7 IEC contactor, TeSys D, nonreversing, 80A resistive, 4 pole, 4 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65004G7
MPN:
LC1D65004G7
Condition:
New
Maximum Operating Rate:
3600 cyc/h 60°C
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Mechanical Durability:
6000000 cycles
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
Reach Free Of Svhc:
Yes
Control Circuit Voltage Limits:
0.3...0.6 Uc 60-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60°C operational AC 50/60 Hz
Compatibility Code:
LC1D
[Ue] Rated Operational Voltage:
power circuit 690 V AC 25...400 Hz
Country of Origin:
United States
Coil Technology:
without built-in bidirectional peak limiting diode suppressor
Warranty:
18 months
Flame Retardance:
V1 conforming to UL 94
Rated Breaking Capacity:
1000 kA at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity:
1000 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for control circuit conforming to IEC 60947-5-1
Overvoltage Category:
III
Contactor Application:
resistive load
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Ui] Rated Insulation Voltage:
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-4-1 || power circuit 690 V IEC 60947-4-1
Height:
122 mm
Poles Description:
4P
Mechanical Robustness:
shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Rohs Exemption Information:
Yes
Pole Contact Composition:
4 NO
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Minimum Switching Current:
5 mA for control circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Inrush Power In Va:
140-140 VA cos phi 0.75 (at 20°C)
Width:
85 mm
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Range Of Product:
TeSys Deca
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Insulation Resistance:
> 10 MOhm for control circuit
Toxic Heavy Metal Free:
Yes
Operating Time:
12...26 ms closing || 4...19 ms opening
Ip Degree Of Protection:
IP2X VDE 0106
Tightening Torque:
control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm hexagonal || power circuit 5 N.m screw clamp terminal Philips No 2 hexagon
Associated Fuse Rating:
10 A gG for control circuit conforming to IEC 60947-5-1 || 125 A at 690 V coordination type 1 for power circuit || 125 A at 690 V coordination type 2 for power circuit
Permissible Ambient Air Temperature Around The Device:
-5-60°C || -40-70°C at Uc
Mounting Support:
rail || plate
Device Short Name:
LC1D
Environmental Disclosure:
ENVPEP110205EN
Mercury Free:
Yes
Average Impedance:
1 mOhm - Ith 80 A 50 Hz for power circuit
Heat Dissipation:
4-5 W at 50/60 Hz for control circuit
Product Certifications:
RINA || CCC || UL || CSA || GL || DNV || LROS (Lloyds register of shipping) || BV || UKCA
$745.92

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 120 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.