Schneider Electric

Schneider Electric LC1D65BD IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D65BD
MPN:
LC1D65BD
Condition:
New
Auxiliary Contacts Type:
mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
Product Certifications:
GOST || LROS (Lloyds register of shipping) || DNV || CCC || CSA || GL || UL || RINA || UKCA
Net Weight:
2.185 kg
Contactor Application:
motor control
Irms Rated Making Capacity:
1000 A at 440 V DC for power circuit conforming to IEC 60947 || 1000 A at 440 V for power circuit conforming to IEC 60947 || 250 A DC for control circuit conforming to IEC 60947-5-1
Protective Cover:
with
Reach Free Of Svhc:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Environmental Disclosure:
ENVPEP110205EN
Toxic Heavy Metal Free:
Yes
Utilisation Category:
AC-3 || AC-2 || AC-1 || AC-3e
Flame Retardance:
V1 conforming to UL 94
Operating Time:
50±15 % ms closing || 20±20 % ms opening
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Control Circuit Voltage Limits:
0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC || 0.1...0.3 Uc -40-70°C drop-out DC
Inrush Power In W:
19-19 W 20°C)
Control Circuit Type:
DC wide range
Pvc Free:
Yes
Safety Reliability Level:
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 || B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
Overvoltage Category:
III
Minimum Switching Current:
5 mA for control circuit
Fire Resistance:
850°C IEC 60695-2-1
Climatic Withstand:
IACS E10 exposure to damp heat
Range Of Product:
TeSys Deca
Standards:
IEC 60947-5-1 || IEC 60947-4-1 || EN 60947-4-1 || UL 508 || EN 60947-5-1
Country of Origin:
United States
Non-Overlap Time:
1.5 ms on energisation between NC and NO contacts || 1.5 ms on de-energisation between NC and NO contacts
Time Constant:
34 ms
Mechanical Robustness:
shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor opened 10 Gn for 11 ms)
Poles Description:
3P
Connections - Terminals:
control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cab
Mechanical Durability:
10000000 cycles
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Range:
TeSys
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Minimum Switching Voltage:
17 V for control circuit
Eu Rohs Directive:
Compliant
Sustainable Offer Status:
Green Premium product
Compatibility Code:
LC1D
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
[Ui] Rated Insulation Voltage:
control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL IEC 60947-1 || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1 || power circuit 1000 V CSA IEC 60947-4-1 || control circuit 600 V CSA
Motor Power Kw:
30 kW at 380...400 V AC 50 Hz || 37 kW at 500 V AC 50 Hz || 37 kW at 660...690 V AC 50 Hz || 18.5 kW at 220...230 V AC 50 Hz || 30 kW at 415 V AC 50 Hz || 37 kW at 1000 V AC 50 Hz (AC-3) || 11 kW at 400 V AC 50 Hz (AC-4) || 30 kW at 440 V AC 50 Hz (A
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Mounting Support:
plate || rail
Maximum Operating Rate:
3600 cyc/h 60°C
$521.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose