Schneider Electric

Schneider Electric LC1D80004U5 IEC contactor, TeSys Deca, nonreversing, 125A resistive, 4 pole, 4 NO, 240VAC 50Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80004U5
MPN:
LC1D80004U5
Condition:
New
Pollution Degree:
3
Ip Degree Of Protection:
IP20 front face IEC 60529
Protective Treatment:
THIEC 60068-2-30
Motor Power Kw:
22 kW at 220...230 V AC 50/60 Hz || 37 kW at 380...400 V AC 50/60 Hz || 45 kW at 660...690 V AC 50/60 Hz || 55 kW at 500 V AC 50/60 Hz || 45 kW at 415...440 V AC 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Altitude:
0...9842.52 ft (0...3000 m)
Average Impedance:
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Flame Retardance:
V1 conforming to UL 94
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V
Weight:
1.76 kg
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60°C) at <= 400 V AC AC-4 for power circuit
[Uc] Control Circuit Voltage:
240 V AC 50 Hz
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Pole Contact Composition:
4 NO
Associated Fuse Rating:
200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Depth:
125 mm
Range Of Product:
TeSys Deca
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Device Short Name:
LC1D
Compatibility Code:
LC1D
[Ue] Rated Operational Voltage:
power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Control Circuit Type:
AC 50 Hz
Fire Resistance:
850°C IEC 60695-2-1
Environmental Disclosure:
ENVPEP110205EN
Range:
TeSys
Sustainable Offer Status:
Green Premium product
Height:
127 mm
Pvc Free:
Yes
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 50 Hz || 1...1.1 Uc 55-70°C operational AC 50 Hz
Hold-In Power Consumption In Va:
20-20 VA 50 Hz cos phi 0.3 (at 20°C)
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Sustainable Packaging:
Yes
Coil Technology:
without built-in suppressor module
Maximum Operating Rate:
3600 cyc/h 60°C
Power Dissipation Per Pole:
12.5 W AC-1
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Poles Description:
4P
Reach Free Of Svhc:
Yes
Protective Cover:
without
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Irms Rated Making Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Rohs Exemption Information:
Yes
$526.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 110A resistive load rating. Contactor is supplied with a 240 VAC 50 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 4.92 inches deep. It weighs 3.88 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose