Schneider Electric

Schneider Electric LC1D80AP7 IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D80AP7
MPN:
LC1D80AP7
Condition:
New
Width:
55 mm
[Ue] Rated Operational Voltage:
power circuit 690 V AC 25...400 Hz || power circuit 300 V DC
Warranty:
18 months
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Compatibility Code:
LC1D
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Electrical Durability:
0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Reach Free Of Svhc:
Yes
Reach Regulation:
Free of Substances of Very High Concern above the threshold
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC-1 for power circuit || 66 A (at <60°C) at <= 440 V AC-3 for power circuit || 66 A (at <60°C) at <= 440 V AC-3e for power circuit
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm²
Pvc Free:
Yes
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Depth:
120 mm
Minimum Switching Voltage:
17 V for Signaling circuit
Overvoltage Category:
III
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Operating Time:
4...19 ms opening || 12...26 ms closing
Hold-In Power Consumption In Va:
13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
Product Or Component Type:
contactor
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Pole Contact Composition:
3 NO
Contactor Application:
resistive load || motor control
Pollution Degree:
3
Fire Resistance:
850°C IEC 60695-2-1
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
Flame Retardance:
V1 conforming to UL 94
Control Circuit Type:
AC 50/60 Hz standard
Maximum Operating Rate:
3600 cyc/h 60°C
Motor Power Kw:
22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 415 V AC 50/60 Hz (AC-3) || 37 kW at 440 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 22 kW at 2
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
Net Weight:
0.86 kg
Sustainable Offer Status:
Green Premium product
Heat Dissipation:
4-5 W at 50/60 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Cover:
with
Country of Origin:
Indonesia
Coil Technology:
without built-in suppressor module
Weight:
0.86 kg
Mounting Support:
plate || rail
Mechanical Durability:
6 Mcycles
Circularity Profile:
ENVEOLI1503009EN
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
$426.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose