Schneider Electric

Schneider Electric LC1DT20B7 IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 4 NO, 24VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT20B7
MPN:
LC1DT20B7
Condition:
New
Compatibility Code:
LC1D
Protective Treatment:
THIEC 60068-2-30
Environmental Disclosure:
ENVPEP1501004
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Insulation Resistance:
> 10 MOhm for Signaling circuit
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 250 A at 440 V for power circuit conforming to IEC 60947
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Height:
85 mm
Operating Time:
4...19 ms opening || 12...22 ms closing
Rohs Exemption Information:
Yes
Heat Dissipation:
2-3 W at 50/60 Hz
Poles Description:
4P
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 20 A (at 60°C) for power circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Country of Origin:
United States
Contactor Application:
resistive load
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Auxiliary Contact Composition:
1 NO + 1 NC
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz
Mechanical Durability:
15 Mcycles
Pollution Degree:
3
Operating Altitude:
0...9842.52 ft (0...3000 m)
Warranty:
18 months
Toxic Heavy Metal Free:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Coil Technology:
without built-in suppressor module
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Ie] Rated Operational Current:
20 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Maximum Operating Rate:
3600 cyc/h 60°C
Sustainable Offer Status:
Green Premium product
Power Dissipation Per Pole:
1.56 W AC-1
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Fire Resistance:
850°C IEC 60695-2-1
Utilisation Category:
AC-1
Pole Contact Composition:
4 NO
[Icw] Rated Short-Time Withstand Current:
30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Pvc Free:
Yes
Minimum Switching Current:
5 mA for Signaling circuit
Eu Rohs Directive:
Compliant
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
$126.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose