Schneider Electric

Schneider Electric LC1DT32F7 IEC contactor, TeSys Deca, nonreversing, 32A resistive, 4 pole, 4 NO, 110VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT32F7
MPN:
LC1DT32F7
Condition:
New
Pvc Free:
Yes
Mechanical Durability:
15 Mcycles
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Overvoltage Category:
III
Range Of Product:
TeSys Deca
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Device Short Name:
LC1D
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.8 N.m screw clamp terminals flat Ø 6 mm || pow
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Product Certifications:
DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
Pole Contact Composition:
4 NO
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Poles Description:
4P
Range:
TeSys || TeSys Deca
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Heat Dissipation:
2-3 W at 50/60 Hz
Protective Treatment:
THIEC 60068-2-30
Operating Altitude:
0...9842.52 ft (0...3000 m)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ip Degree Of Protection:
IP20 front face IEC 60529
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Fire Resistance:
850°C IEC 60695-2-1
Environmental Disclosure:
ENVPEP1501004
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Circularity Profile:
ENVEOLI1501004
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Country of Origin:
Singapore
Depth:
99 mm
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Coil Technology:
without built-in suppressor module
Contactor Application:
resistive load
Electrical Durability:
1 Mcycles 32 A AC-1 <= 440 V
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Minimum Switching Current:
5 mA for Signaling circuit
Control Circuit Type:
AC 50/60 Hz
Maximum Operating Rate:
3600 cyc/h 60°C
Toxic Heavy Metal Free:
Yes
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Auxiliary Contact Composition:
1 NO + 1 NC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Operating Time:
4...19 ms opening || 12...22 ms closing
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
$189.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.