Schneider Electric

Schneider Electric LC1G1504KUEN Contactor, high power, TeSys Giga, standard version, 4 pole/NO, AC-1 <=440V 275A, 100-250VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G1504KUEN
MPN:
LC1G1504KUEN
Condition:
New
Protective Treatment:
TH
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
[Ith] Conventional Free Air Thermal Current:
275 A (at 40°C)
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Depth:
193 mm
Halogen Content Performance:
Halogen free plastic parts product
Compatibility Code:
LC1G
Weight:
4.4 kg
China Rohs Regulation:
X
Mercury Free:
Yes
Hold-In Power Consumption In W:
7.8-7.8 W
Pole Contact Composition:
4 NO
Auxiliary Contact Composition:
1 NO + 1 NC
Inrush Power In Va:
540-540 VA
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Connection Pitch:
35 mm
Poles Description:
4P
Environmental Disclosure:
ENVPEP2105013
Average Impedance:
0.00018 Ohm
Mounting Support:
plate
Associated Fuse Rating:
160 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Icw] Rated Short-Time Withstand Current:
1.2 kA - 10 s || 0.7 kA - 30 s || 0.6 kA - 1 min || 0.45 kA - 3 min || 0.35 kA - 10 min
Device Short Name:
LC1G
Width:
143 mm
Mechanical Durability:
8 Mcycles
[Uc] Control Circuit Voltage:
100...250 V AC 50/60 Hz || 100...250 V DC
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-5a || AC-5b || AC-6a || AC-6b || DC-1 || DC-3 || DC-5
Eu Rohs Directive:
Compliant with Exemptions
Hold-In Power Consumption In Va:
12.4-12.4 VA
Pvc Free:
Yes
Range Of Product:
TeSys Giga
Irms Rated Making Capacity:
1890 A at 440 V
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1
Country of Origin:
China
Power Dissipation Per Pole:
10 W AC-1 - Ith 275 A || 5 W AC-3 - Ith 150 A
Rated Breaking Capacity:
1280 A at 440 V
Inrush Power In W:
380 W
Net Weight:
4.4 kg
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Ui] Rated Insulation Voltage:
1000 V
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Ambient Air Temperature For Storage:
-60-80°C
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
[Ie] Rated Operational Current:
150 A (at <60°C) at <= 440 V AC-3 || 275 A (at <40°C) at <= 1000 V AC-1
Operating Time:
40...70 ms closing || 15...50 ms opening
$970.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 275A @440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose