Schneider Electric

Schneider Electric LC1G265EHEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 265A, 3 pole/NO, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G265EHEA
MPN:
LC1G265EHEA
Condition:
New
Height:
290 mm
Eu Rohs Directive:
Compliant with Exemptions
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
[Ith] Conventional Free Air Thermal Current:
385 A (at 40°C)
Color:
dark grey
Mercury Free:
Yes
Overvoltage Category:
III
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Power Dissipation Per Pole:
20 W AC-1 - Ith 385 A || 11 W AC-3 - Ith 265 A
Environmental Disclosure:
ENVPEP2105013
Net Weight:
8.2 kg
Operating Time:
40...70 ms closing || 15...50 ms opening
Coil Technology:
built-in bidirectional peak limiting
Halogen Content Performance:
Halogen free plastic parts product
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
Auxiliary Contact Composition:
1 NO + 1 NC
[Ui] Rated Insulation Voltage:
1000 V
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Range Of Product:
TeSys Giga
Circularity Profile:
ENVEOLI2105013
Pole Contact Composition:
3 NO
Mechanical Durability:
8 Mcycles
Rated Breaking Capacity:
2380 A at 440 V
Average Impedance:
0.000144 Ohm
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Sustainable Offer Status:
Green Premium product
Product Or Component Type:
contactor
Device Short Name:
LC1G
Pvc Free:
Yes
Inrush Power In Va:
430-430 VA
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Mounting Support:
plate
Motor Power Kw:
75 kW at 230 V AC 50/60 Hz (AC-3e) || 132 kW at 400 V AC 50/60 Hz (AC-3e) || 132 kW at 415 V AC 50/60 Hz (AC-3e) || 160 kW at 440 V AC 50/60 Hz (AC-3e) || 160 kW at 500 V AC 50/60 Hz (AC-3e) || 200 kW at 690 V AC 50/60 Hz (AC-3e) || 160 kW at 1000 V
Range:
TeSys
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Hold-In Power Consumption In Va:
11.7-11.7 VA
Irms Rated Making Capacity:
3320 A at 440 V
Inrush Power In W:
360 W
Rohs Exemption Information:
Yes
Connection Pitch:
45 mm
Tightening Torque:
35 N.m
Weight:
8.2 kg
Associated Fuse Rating:
315 A aM at <= 440 V for motor || 250 A aM at <= 690 V for motor || 400 A gG at <= 690 V
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
$1,570.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 265A 160kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.