Schneider Electric LC1K0901M7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NC aux., 220 to 230VAC coil
Schneider Electric
$75.00
LC1K0901M7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 220V 50/60Hz AC coil and 1NC auxiliary contact. LC1K0901M7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 220V 50/60Hz AC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
- Environmental Disclosure:
- ENVPEP1503003EN
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Product Or Component Type:
- contactor
- Minimum Switching Current:
- 5 mA for Signaling circuit
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Control Circuit Type:
- AC 50/60 Hz
- Poles Description:
- 3P
- Non Overlap Distance:
- 0.5 mm
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Mechanical Durability:
- 10 Mcycles
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Country of Origin:
- Indonesia
- Eu Rohs Directive:
- Compliant
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Auxiliary Contact Composition:
- 1 NC
- Circularity Profile:
- ENVEOLI1503003EN
- Signaling Circuit Frequency:
- <= 400 Hz
- Overvoltage Category:
- III
- Range:
- TeSys
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Device Short Name:
- LC1K
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Maximum Operating Rate:
- 3600 cyc/h
- Device Application:
- control
- Warranty:
- 18 months
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Toxic Heavy Metal Free:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application:
- motor control || resistive load
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Reach Free Of Svhc:
- Yes
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Pole Contact Composition:
- 3 NO
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Depth: