Schneider Electric LC2D09G7 TeSys Deca IEC contactor, 9 A, 3 P, 5 HP at 480 VAC, reversing, 120 VAC 50/60 Hz coil
Schneider Electric
$287.64
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Mounting Support:
- plate || rail
- Circularity Profile:
- ENVEOLI1501004
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Pole Contact Composition:
- 3 NO
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Width:
- 90 mm
- Maximum Horse Power Rating:
- 0.5 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp
- Toxic Heavy Metal Free:
- Yes
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Average Impedance:
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Flame Retardance:
- V1 conforming to UL 94
- Overvoltage Category:
- III
- Contactor Application:
- resistive load || motor control
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Power Dissipation Per Pole:
- 0.2 W AC-3 || 1.56 W AC-1
- Utilisation Category:
- AC-1 || AC-3
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Device Presentation:
- preassembled with reversing power busbar
- Motor Power Kw:
- 2.2 kW at 220...230 V AC 50 Hz || 4 kW at 380...400 V AC 50 Hz || 4 kW at 415...440 V AC 50 Hz || 5.5 kW at 500 V AC 50 Hz || 5.5 kW at 660...690 V AC 50 Hz
- Protective Cover:
- with
- Control Circuit Type:
- AC 50/60 Hz
- Range:
- TeSys || TeSys Deca
- Depth:
- 86 mm
- Product Or Component Type:
- reversing contactor
- Poles Description:
- 3P
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Environmental Disclosure:
- ENVPEP1501004
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Electrical Durability:
- 0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
- Height:
- 77 mm
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Product Name:
- TeSys D || TeSys Deca
- Net Weight:
- 0.687 kg
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Eu Rohs Directive:
- Compliant
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Mechanical Durability: