- Fire Resistance:
- 850°C IEC 60695-2-1
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Sustainable Offer Status:
- Green Premium product
- Power Dissipation Per Pole:
- 0.8 W AC-3 || 2.5 W AC-1 || 0.8 W AC-3e
- [Icw] Rated Short-Time Withstand Current:
- 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Overvoltage Category:
- III
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
- Mounting Support:
- plate || rail
- Electrical Durability:
- 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V || 1.65 Mcycles 18 A AC-3e <= 440 V
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Contactor Application:
- resistive load || motor control
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Device Short Name:
- LC2D
- [Uc] Control Circuit Voltage:
- 24 V AC 50/60 Hz
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Eu Rohs Directive:
- Compliant
- Product Name:
- TeSys Deca
- Country of Origin:
- France
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Maximum Horse Power Rating:
- 1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at
- Weight:
- 0.707 kg
- Average Impedance:
- 2.5 mOhm - Ith 32 A 50 Hz for power circuit
- Heat Dissipation:
- 2-3 W 50/60 Hz
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Rohs Exemption Information:
- Yes
- Pvc Free:
- Yes
- Range:
- TeSys || TeSys Deca
- Net Weight:
- 0.707 kg
- Protective Cover:
- with
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Pollution Degree:
- 3
- Mercury Free:
- Yes
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Rated Breaking Capacity:
- 300 A at 440 V for power circuit conforming to IEC 60947
- Control Circuit Type:
- AC 50/60 Hz
- Device Presentation:
- preassembled with reversing power busbar
- Warranty:
- 18 months
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- [Ie] Rated Operational Current:
- 18 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60°C) at <= 440 V AC AC-3e for power circuit