Schneider Electric

Schneider Electric LC2D18EHE TeSys Deca reversing contactor - 3P - <= 440 V - 18 A AC-3 - 48...130 V AC/DC coil

(No reviews yet) Write a Review
SKU:
LC2D18EHE
MPN:
LC2D18EHE
Condition:
New
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Protective Treatment:
TH IEC 60068-2-30
Maximum Horse Power Rating:
1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at
Inrush Power In W:
24-24 W 20°C
Weight:
0.803 kg
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
Coil Technology:
built-in bidirectional peak limiting
Overvoltage Category:
III
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Ambient Air Temperature For Storage:
-60-80°C
Circularity Profile:
ENVEOLI1609001EN
Hold-In Power Consumption In Va:
1.3-1.3 VA 20°C) 50/60 Hz
Mercury Free:
Yes
Contactor Application:
resistive load || motor control
Device Presentation:
preassembled with reversing power busbar
Hold-In Power Consumption In W:
0.8-0.8 W 20°C
Mechanical Durability:
15 Mcycles
Depth:
86 mm
Inrush Power In Va:
25-25 VA 50/60 Hz 20°C)
Flame Retardance:
V1 conforming to UL 94
Rohs Exemption Information:
Yes
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Electrical Durability:
2.2 Mcycles 15 A AC-3 <= 440 V || 0.9 Mcycles 32 A AC-1 <= 440 V || 2.2 Mcycles 15 A AC-3e <= 440 V
Range:
TeSys || TeSys Deca
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power
Eu Rohs Directive:
Compliant with Exemptions
Pollution Degree:
3
Operating Altitude:
0...9842.52 ft (0...3000 m)
Maximum Operating Rate:
3600 cyc/h 60°C
Warranty:
18 months
Mounting Support:
plate || rail
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
Auxiliary Contact Composition:
1 NO + 1 NC
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Device Short Name:
LC2D
[Icw] Rated Short-Time Withstand Current:
40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Connections - Terminals:
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
Operating Time:
45...55 ms closing || 20...90 ms opening
Minimum Switching Current:
5 mA for Signaling circuit
[Ith] Conventional Free Air Thermal Current:
32 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Protective Cover:
with
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
$160.00

Description

LC2D18EHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 18A AC-3 7.5kW@400V, it includes a 48-130V AC/DC low consumption electronic coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D18EHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 7.5kW@400V. It includes a 48-130V AC/DC low consumption electronic coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 18A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.
View AllClose