Schneider Electric

Schneider Electric LC2D25G7 TeSys Deca IEC contactor, 25 A, 3 P, 15 HP at 480 VAC, reversing, 120 VAC 50/60 Hz coil

(No reviews yet) Write a Review
SKU:
LC2D25G7
MPN:
LC2D25G7
Condition:
New
Pole Contact Composition:
3 NO
Contactor Application:
motor control || resistive load
[Icw] Rated Short-Time Withstand Current:
50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Rohs Exemption Information:
Yes
Net Weight:
0.787 kg
Coil Technology:
without built-in suppressor module
Country of Origin:
United States
Connections - Terminals:
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
Maximum Operating Rate:
3600 cyc/h 60°C
Auxiliary Contact Composition:
1 NO + 1 NC
Ip Degree Of Protection:
IP20 front face IEC 60529
Signaling Circuit Frequency:
25...400 Hz
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Maximum Horse Power Rating:
3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 hp
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Protective Cover:
with
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Product Name:
TeSys Deca
Utilisation Category:
AC-1 || AC-3 || AC-3e
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Minimum Switching Voltage:
17 V for Signaling circuit
Interlocking Type:
mechanical
Depth:
92 mm
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Warranty:
18 months
Power Dissipation Per Pole:
1.25 W AC-3 || 3.2 W AC-1 || 1.25 W AC-3e
Range:
TeSys || TeSys Deca
Operating Time:
12...22 ms closing || 4...19 ms opening
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Mechanical Durability:
15 Mcycles
Product Certifications:
DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA || CB
Pvc Free:
Yes
Control Circuit Type:
AC 50/60 Hz
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Sustainable Offer Status:
Green Premium product
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Width:
90 mm
Eu Rohs Directive:
Compliant
Height:
85 mm
Electrical Durability:
1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Product Or Component Type:
reversing contactor
$462.12

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).