Schneider Electric

Schneider Electric LR9G630 Thermal overload relay, electronic, TeSys Giga, 160A to 630A, Class 5E to 30E, push-in control connection

(No reviews yet) Write a Review
SKU:
LR9G630
MPN:
LR9G630
Condition:
New
Weight:
2.67 kg
Thermal Protection Adjustment Range:
160-630 A
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Net Weight:
2.67 kg
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60335-1
Device Short Name:
LR9G
Reset:
automatic reset || manual
Thermal Overload Class:
class 5E...30E IEC 60947-4-1
Mercury Free:
Yes
Local Signaling:
LED || trip indicator
Product Name:
TeSys LRG
Environmental Disclosure:
ENVPEP2105014
California Proposition 65:
WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive h
Ambient Air Temperature For Operation:
-25-60°C
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
Circularity Profile:
ENVEOLI2105014
Product Certifications:
CB Scheme || CCC || cULus || UKCA || ATEX || EU-RO-MR by DNV-GL || EAC
Protection Type:
ground fault protection 0-1 s - alarm circuit IEC 60947-4-1 || ground fault protection 0-1 s - alarm circuit UL 60947-4-1 || phase loss 0-4 s - alarm circuit || phase imbalance 0-5 s - alarm circuit IEC 60947-4-1 || phase imbalance 0-5 s - alarm circ
Country of Origin:
France
Color:
dark grey
Tightening Torque:
58 N.m
Permissible Ambient Air Temperature Around The Device:
-40-60°C at Uc
Protective Treatment:
TH
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mechanical Robustness:
vibrations 5-300 Hz 6 gn contactor open || shocks 15 gn 11 ms contactor closed
Connections - Terminals:
power circuit: bar - busbar cross section: 50 x 10 mm || power circuit: lugs-ring terminals 1 300-300 mm² || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - ca
Contacts Type And Composition:
1 NO + 1 NC
[Ue] Rated Operational Voltage:
1000 V AC 50/60 Hz
China Rohs Regulation:
X
Mechanical Durability:
7000 cycles
Halogen Content Performance:
Halogen free plastic parts product
Product Or Component Type:
electronic thermal overload relay
Tripping Threshold:
1.125 +/- 0.07 In IEC 60947-4-1
Ambient Air Temperature For Storage:
-60-80°C
Overvoltage Category:
III
[Ith] Conventional Free Air Thermal Current:
0.208333333333333
Surge Withstand:
4 kV
Ambient Air Transport Temperature:
-25-60°C
Network Type:
AC
Range:
TeSys
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Depth:
186 mm
Mounting Support:
direct on contactor || plate
Eu Rohs Directive:
Compliant with Exemptions
Relay Application:
motor protection
$1,690.00

Description

TeSys LR9G 630A thermal overload relay is compatible with TeSys Giga high power contactor, push-in control connection. It provides phase imbalance, phase failure, in-built ground-fault and single-phase loads protections. It is available for manual and auto reset options and LED indicator for Motor ON and pre-trip alarm. Tripping classes is selectable from class 5E to class 30E to suit different application needs from fast tripping, general purpose and high inertia loads. It is suitable for independent mounting or direct mounting with LC1G contactors. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature without derating up to 3000m altitude. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose