Schneider Electric

Schneider Electric SSP01EMA12S Surge protection device, Surgelogic, 120kA, 120/240 VAC, 1 phase, 3 wire, NEMA 4X

(No reviews yet) Write a Review
SKU:
SSP01EMA12S
MPN:
SSP01EMA12S
Condition:
New
Phase:
1 phase
Length:
483 mm
Rohs Exemption Information:
Yes
Depth:
238.8 mm
Ambient Air Temperature For Operation:
65-65°C
Local Signaling:
status LED green per phase normal operation || status LED red per phase fault
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Mounting:
surface
Cable Length:
483 mm
Connections - Terminals:
lugs AWG 10...AWG 2 copper 4 N.m
[Uc] Maximum Continuous Operating Voltage:
150 V
Short-Circuit Protection:
200 kA
Device Short Name:
EMA
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
[Ue] Rated Operational Voltage:
120/240 V AC
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Standards:
CSA C22.2 No 8 || UL 1449:ed. 4 || UL 1283:ed. 5
Country of Origin:
Mexico
Nema Degree Of Protection:
NEMA 4X
Mercury Free:
Yes
Enclosure Material:
Stainless Steel
Nominal Discharge Current:
20 kA
Surge Current:
120 kA
Eu Rohs Directive:
Compliant with Exemptions
Wiring Configuration:
3-wire
Range Of Product:
Surgelogic
Provided Equipment:
alarm enable/disable switch || surge counter || dry contacts
Product Or Component Type:
surge protection device
$4,774.35

Description

Surgelogic™ Type EMA Series surge protective devices deliver specification grade performance for service entrance or critical branch panel applications. These multi-phase surge suppression systems provide transient suppression, noise filtration in a durable modular package. They provide better performance with a diagnostic interface with push to test switches, red and green status LEDs, module status LEDs per mode, dry contacts, audible alarm with disable switch, and a surge counter. It has 10 year product warranty.
View AllClose