WAGO 787-1601

(No reviews yet) Write a Review
SKU:
787-1601
MPN:
787-1601
Condition:
New
conformity marking:
CE
connection technology:
CAGE CLAMP
connection type 1:
Input/output/signaling
control deviation:
¤ 1 %
country of origin sales organisation germany:
DE
current limitation:
1.1 x Io nom (typ.)
default setting:
DC 12 V
depth from upper edge of din rail:
107.5 mm / 4.232 inch
derating:
-3 %/K (> 50 C)
discharge current:
¤ 0.25 mA
efficiency typ:
0.82
fine stranded conductor:
0.08 2.5 mm / 28 12 AWG
fire load:
0.000 MJ
height:
90 mm / 3.543 inch
input current ii:
¤ 0.29 A (240 VAC): ¤ 0.5 A (100 VAC)
input voltage derating:
-2.5 %/V (< 95 VAC)
input voltage range:
AC 85 264 V: DC 120 372 V
inrush current:
¤ 30 A
internal fuse:
T 2 A / 250 VAC
isolation voltage pri sec:
DC 4.242 kV
mains failure hold up time:
120 ms (230 VAC): 15 ms (100 VAC)
mounting type:
DIN-35 rail
mtbf:
> 500,000 h (per IEC 61709)
nominal input voltage ui nom:
1 x AC 100 240 V
nominal mains frequency range:
44 66 Hz: 0 Hz
nominal output current io nom:
2 A (12 VDC): 2.1 A (< 40 C)
nominal output power:
24 W
nominal output voltage uo nom:
DC 12 V (SELV)
open circuit proof:
Yes
operation status indicator:
Green LED (Uo)
output voltage range:
DC 11.5 14.5 V (adjustable)
overload behavior:
Constant current
overvoltage category:
II
overvoltage protection secondary:
Internal protective circuit || ¤ 35 VDC (in the event of a fault)
packaging type:
Box
parallel operation:
Yes
phases:
1
pollution degree:
2
power factor correction pfc:
Passive
power loss max pl max:
5.7 W (100 VAC / 12 VDC: 2 A)
power loss pl:
¤ 0.7 W (230 VAC: No load): ¤ 5.3 W (230 VAC: Nominal load)
protection class:
II
protection type:
IP20 (per EN 60529)
recommended backup fusing:
Circuit breaker: 6 A, 10 A, 16 A: Tripping characteristic: B or C
relative humidity:
5 96 % (no condensation permissible)
required backup fusing:
An external DC fuse is required for the DC input voltage.
residual ripple:
¤ 20 mV (Peak-to-peak)
resistance to reverse feed:
¤ DC 25 V
series operation:
Yes
short circuit protected:
Yes
signaling:
1 x LED DC OK (green) || 1 x Active signal output DC OK (12 VDC: 40 mA)
solid conductor:
0.08 2.5 mm / 28 12 AWG
standards specifications:
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || EN 60335-1 || UL 60950-1 || UL 508 || GL
strip length:
8 9 mm / 0.31 0.35 inch
surrounding air temperature operation:
-25 70 C (Device starts at 40 C (type-tested))
surrounding air temperature storage:
-25 85 C
transient suppression primary:
Varistor
wago connector:
WAGO 721 Series
weight:
128.000 g
width:
22.5 mm / 0.886 inch
  • Wago 787-1601
  • Wago 787-1601
  • Wago 787-1601
$102.50

Description

  • Switched-mode power supply
  • Natural convection cooling when horizontally mounted
  • Enclosed for use in switchgear cabinets
  • Limited Power Source (LPS) per NEC Class 2
  • Bounce-free switching signal (DC O K)
  • Suitable for both parallel and series operation
  • Electrically isolated output voltage (SELV) per EN 60950-1/UL 60950-1; PELV per EN 60204
  • GL approval, also suitable for EMC 1 in conjunction with 787-980 Filter Module
View AllClose