- Communication Interface:
- Modbus || Ethernet
- Poles Description:
- 3P
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Magnetic Tripping Current:
- 750-750 A
- Quality Labels:
- CE
- Mounting Support:
- lug
- Suitability For Isolation:
- yes IEC 60947-2
- Wire Stripping Length:
- 16 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Length:
- 16 mm
- Breaking Capacity Code:
- G
- Ambient Air Temperature For Storage:
- -50-85°C
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Operation:
- -25-70°C
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Continuous Current Rating:
- 0.8
- Network Frequency:
- 50/60 Hz
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- terminal nut, line || lugs, load
- Utilisation Category:
- category A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Protected Poles Description:
- 3t
- Eu Rohs Directive:
- Compliant
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Sustainable Offer Status:
- Green Premium product
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Control Type:
- toggle
- Quantity Per Set:
- 1
- Depth:
- 86 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Range:
- PowerPact
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Magnetic Hold Current:
- 350 A
- Weight:
- 2.2 kg
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount lug)
- Pollution Degree:
- 3 IEC 60947-1
- Device Application:
- distribution
- Trip Unit Technology:
- thermal-magnetic
- Circularity Profile:
- ENVEOLI1311006EN
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3