Schneider Electric

Schneider Electric HJP36070 Circuit breaker, PowerPacT H, 70A, 3 pole, 600VAC, 25kA, lugs, thermal magnetic, 80%

(No reviews yet) Write a Review
SKU:
HJP36070
MPN:
HJP36070
Condition:
New
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Mounting Support:
lug
Pvc Free:
Yes
Product Certifications:
UL || CSA || NOM
Quantity Per Set:
1
Terminal Identifier:
AL150HD
Line Rated Current:
70-70 A
Weight:
2.2 kg
Warranty:
18 months
Utilisation Category:
category A
Ambient Air Temperature For Operation:
-25-70°C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Mercury Free:
Yes
Device Application:
distribution
Ambient Air Temperature For Storage:
-50-85°C
Circuit Breaker Application:
HACR rated
Electrical Connection:
terminal nut, line || lugs, load
Depth:
86 mm
Wire Stripping Length:
16 mm
Environmental Disclosure:
ENVPEP1311006EN
Network Frequency:
50/60 Hz
Range:
PowerPact
Suitability For Isolation:
yes IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Color:
Black
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Mounting Mode:
unit mount lug)
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Continuous Current Rating:
0.8
Sustainable Offer Status:
Green Premium product
Pollution Degree:
3 IEC 60947-1
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Protected Poles Description:
3t
Ip Degree Of Protection:
front cover IP40 IEC 60529
Circularity Profile:
ENVEOLI1311006EN
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Magnetic Tripping Current:
1450-1450 A
Length:
16 mm
Net Weight:
2.2 kg
Trip Unit Technology:
thermal-magnetic
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Eu Rohs Directive:
Compliant
Magnetic Hold Current:
800 A
Poles Description:
3P
$4,722.75

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has terminal nuts on the line side and lugs on the load side. This PowerPacT H, 70A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.