Schneider Electric

Schneider Electric LADT4 Time delay auxiliary contact block, TeSys Deca, 1NO + 1NC, on delay 10-180s, front, screw clamp terminals

(No reviews yet) Write a Review
SKU:
LADT4
MPN:
LADT4
Condition:
New
Product Or Component Type:
time delay auxiliary contact block
[Ue] Rated Operational Voltage:
690 V AC 25...400 Hz
Time Delay Range:
10...180 s
Auxiliary Contacts Operation:
time delay
Country of Origin:
United States
Minimum Switching Voltage:
17 V
Warranty:
18 months
Rohs Exemption Information:
Yes
Connections - Terminals:
screw clamp terminals 1 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-2.5 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible without cable end
Range:
TeSys || TeSys Deca
Environmental Characteristic:
normal environment
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mechanical Durability:
5 Mcycles
Product Certifications:
IECEE CB Scheme || UL || CSA || CCC || EAC || UKCA
[Ie] Rated Operational Current:
6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
Ambient Air Temperature For Operation:
-40-70°C
Mounting Location:
front
Mercury Free:
Yes
Depth:
61 mm
Range Compatibility:
TeSys Deca CAD || TeSys Deca LC1D || TeSys F LC1F || TeSys F CR1F
Ip Degree Of Protection:
IP20 conforming to IEC 60529
Sustainable Packaging:
Yes
Pole Contact Composition:
1 NO + 1 NC
[Ui] Rated Insulation Voltage:
690 V IEC 60947-5-1 || 600 V UL 60947-5-1 || 600 V CSA C22.2 No 60947-5-1
Minimum Switching Current:
5 mA
Protective Treatment:
TH IEC 60068
Environmental Disclosure:
ENVPEP110702EN_V01
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Circularity Profile:
N/A
Insulation Resistance:
> 10 MOhm
Non-Overlap Time:
1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
Ambient Air Temperature For Storage:
-60-80°C
Product Name:
TeSys Deca
Pvc Free:
Yes
California Proposition 65:
WARNING: Cancer - www.P65Warnings.ca.gov
Operating Altitude:
9842.52 ft (3000 m)
Tightening Torque:
1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
Permissible Short-Time Rating:
100 A 60°C 1 s || 120 A 60°C 500 ms || 140 A 60°C 100 ms
Protection Type:
gG fuse 10 A
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Sustainable Offer Status:
Green Premium product
Irms Rated Making Capacity:
140 A at <= 690 V AC conforming to IEC 60947-5-1 || 250 A at <= 690 V DC conforming to IEC 60947-5-1
Eu Rohs Directive:
Compliant with Exemptions
Color:
dark grey
Timer Type:
on delay
$157.20

Description

TeSys Deca time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, On-delay setting range 10-180s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).