Schneider Electric

Schneider Electric LC1D099G7 IEC contactor, TeSys D, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D099G7
MPN:
LC1D099G7
Condition:
New
Toxic Heavy Metal Free:
Yes
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Mercury Free:
Yes
Operating Time:
12...22 ms closing || 4...19 ms opening
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Overvoltage Category:
III
Connections - Terminals:
control circuit: Faston terminals 1 || power circuit: plug-in connector
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Minimum Switching Current:
5 mA for Signaling circuit
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Insulation Resistance:
> 10 MOhm for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Operating Altitude:
0...9842.52 ft (0...3000 m)
Sustainable Offer Status:
Green Premium product
Power Dissipation Per Pole:
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
Flame Retardance:
V1 conforming to UL 94
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
Signaling Circuit Frequency:
25...400 Hz
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Minimum Switching Voltage:
17 V for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Maximum Horse Power Rating:
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
Device Short Name:
LC1D
Weight:
0.32 kg
Circularity Profile:
ENVEOLI1501004
Poles Description:
3P
Control Circuit Type:
AC 50/60 Hz
Range Of Product:
TeSys Deca
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Depth:
86 mm
Ip Degree Of Protection:
IP20 front face IEC 60529
Rohs Exemption Information:
Yes
Contactor Application:
resistive load || motor control
Mechanical Durability:
15 Mcycles
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Mounting Support:
rail || plate
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Warranty:
18 months
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Country of Origin:
France
Product Or Component Type:
contactor
Heat Dissipation:
2-3 W at 50/60 Hz
$112.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Plug-in connectors are used for the load connections and Faston terminals for the control circuit. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.