- Fire Resistance:
- 850°C IEC 60695-2-1
- Pole Contact Composition:
- 3 NO
- Minimum Switching Voltage:
- 17 V for control circuit
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Minimum Switching Current:
- 5 mA for control circuit
- Reach Free Of Svhc:
- Yes
- Standards:
- IEC 60947-4-1 || CSA C22.2 No 14 || UL 508 || IEC 60947-5-1 || EN 60947-4-1 || EN 60947-5-1
- Connections - Terminals:
- control circuit 1 1-4 mm²flexible with cable end || power circuit 2 1-25 mm²flexible with cable end || power circuit 2 1-25 mm²flexible without cable end || power circuit 2 1-25 mm²solid without cable end || power circuit 2 1-35 mm²flexible with
- Overvoltage Category:
- III
- Interlocking Type:
- mechanical
- Product Or Component Type:
- reversing contactor
- Device Short Name:
- LC2D
- Sustainable Offer Status:
- Green Premium product
- Control Circuit Voltage Limits:
- drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60°C) || operational: 0.8...1.1 Uc at 50 Hz (at <60°C) || operational: 0.85...1.1 Uc at 60 Hz (at <60°C)
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Range Of Product:
- TeSys Deca
- Mercury Free:
- Yes
- Insulation Resistance:
- > 10 MOhm for control circuit
- Ambient Air Temperature For Storage:
- -60-80°C
- Circularity Profile:
- N/A
- Warranty:
- 18 months
- Rated Breaking Capacity:
- 900 A at 440 V for power circuit conforming to IEC 60947
- Protective Treatment:
- TH 3)IEC 60068
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Control Circuit Type:
- AC
- Coil Type:
- standard
- Product Certifications:
- GL || UL || RINA || GOST || CSA || LROS (Lloyds register of shipping) || CCC || DNV || BV || UKCA
- Flame Retardance:
- V1 conforming to UL 94
- Environmental Disclosure:
- ENVPEP110205EN
- Net Weight:
- 2.4 kg
- Height:
- 132 mm
- Vibration Resistance:
- 2 gn 5-300 Hz contactor opened || 3 gn 5-300 Hz contactor closed
- Coil Technology:
- without built-in bidirectional peak limiting diode suppressor
- Heat Dissipation:
- 6-10 W at 50/60 Hz for control circuit
- Toxic Heavy Metal Free:
- Yes
- Permissible Ambient Air Temperature Around The Device:
- -40-70°C at Uc
- Hold-In Power Consumption In Va:
- 20-20 VA 50 Hz cos phi 0.3 (at 20°C) || 22-22 VA 60 Hz cos phi 0.3 (at 20°C) || 26-26 VA 50 Hz cos phi 0.3 (at 20°C) || 26-26 VA 60 Hz cos phi 0.3 (at 20°C)
- Mechanical Durability:
- 6000000 cycles
- Protective Cover:
- with
- Weight:
- 2.4 kg
- [Ui] Rated Insulation Voltage:
- control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
- Motor Power Kw:
- 15 kW 220...240 V AC 50/60 Hz || 22 kW 380...400 V AC 50/60 Hz || 25 kW 415 V AC 50/60 Hz || 30 kW 440 V AC 50/60 Hz || 30 kW 500 V AC 50/60 Hz || 33 kW 660...690 V AC 50/60 Hz
- Mounting Support:
- plate || rail
- Shock Resistance:
- 10 gn contactor closed || 8 gn contactor opened
- Ambient Air Temperature For Operation:
- -5-60°C
- [Ue] Rated Operational Voltage:
- power circuit <= 1000 V AC 25...400 Hz
- Pvc Free:
- Yes
- Operating Time:
- 12...26 ms closing || 4...19 ms opening