Schneider Electric LJL36400U53X Circuit breaker, PowerPacT L, 400A, 3 pole, 600VAC, 25kA, lugs, MicroLogic 5.3E, 80%
Schneider Electric
$10,976.00
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Energy with a 5.3E trip unit and an LSI function. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Ambient Air Temperature For Storage:
- -50-85°C
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- Mounting Support:
- lug
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Trip Unit Technology:
- electronic, energy, MicroLogic 5.3 E, LSI
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Weight:
- 6.2 kg
- Product Name:
- PowerPact L
- Circuit Breaker Application:
- HACR rated
- Range:
- PowerPact
- Eu Rohs Directive:
- Compliant with Exemptions
- Device Short Name:
- L-Frame
- Length:
- 31 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Terminal Identifier:
- AL600LS52K3
- Net Weight:
- 6.2 kg
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Circularity Profile:
- ENVEOLI2206029EN
- Pollution Degree:
- 3 IEC 60947-1
- Breaking Capacity Code:
- J
- Country of Origin:
- United States
- Environmental Disclosure:
- ENVPEP2206029EN
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ip Degree Of Protection:
- front cover IP40
- Mercury Free:
- Yes
- Electrical Connection:
- lugs, line || lugs, load
- Line Rated Current:
- 400-400 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Device Application:
- distribution
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Depth:
- 110 mm
- Communication Interface:
- Modbus || Ethernet
- Protection Technology:
- current limiter
- Warranty:
- 18 months
- Suitability For Isolation:
- yes IEC 60947-2
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 31 mm || 61 mm