- Trip Unit Technology:
- thermal-magnetic
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- Breaking Capacity Code:
- L
- Width:
- 104 mm
- Color:
- Black
- Network Frequency:
- 50/60 Hz
- Device Application:
- distribution
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Poles Description:
- 2P
- Wire Stripping Length:
- 16 mm
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Length:
- 16 mm
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Net Weight:
- 2.2 kg
- Quality Labels:
- CE
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Utilisation Category:
- category A
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- ENVEOLI2206027EN
- Rohs Exemption Information:
- Yes
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP2206027EN
- Magnetic Hold Current:
- 350 A
- Depth:
- 86 mm
- Pollution Degree:
- 3 IEC 60947-1
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Range:
- PowerPact
- Protected Poles Description:
- 2t
- Electrical Connection:
- lugs, line || lugs, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Or Component Type:
- circuit breaker
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Line Rated Current:
- 25-25 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Weight:
- 2.2 kg
- Mercury Free:
- Yes
- Country of Origin:
- United States
- Mounting Mode:
- unit mount lug)
- Ambient Air Temperature For Storage:
- -50-85°C
- Product Certifications:
- UL || CSA || NOM
- Pvc Free:
- Yes
- Circuit Breaker Application:
- HACR rated