[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Signaling Circuit Frequency:
25...400 Hz
Poles Description:
3P
Country of Origin:
Indonesia
Time Constant:
28 ms
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Environmental Disclosure:
ENVPEP110230EN
Weight:
0.54 kg
Mechanical Durability:
30 Mcycles
Auxiliary Contact Composition:
1 NO + 1 NC
Depth:
101 mm
Power Dissipation Per Pole:
5 W AC-1 || 3 W AC-3 || 3 W AC-3e
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Flame Retardance:
V1 conforming to UL 94
Contactor Application:
resistive load || motor control
Protective Treatment:
THIEC 60068-2-30
Operating Altitude:
0...9842.52 ft (0...3000 m)
Device Short Name:
LC1D
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Insulation Resistance:
> 10 MOhm for Signaling circuit
Eu Rohs Directive:
Compliant with Exemptions
Rohs Exemption Information:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Pollution Degree:
3
Inrush Power In W:
5.4-5.4 W 20°C)
Protective Cover:
with
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
[Ie] Rated Operational Current:
50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Mounting Support:
rail || plate
Compatibility Code:
LC1D
Mercury Free:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Sustainable Offer Status:
Green Premium product
Warranty:
18 months
[Icw] Rated Short-Time Withstand Current:
60 A 40°C - 10 min for power circuit || 430 A 40°C - 1 s for power circuit || 150 A 40°C - 1 min for power circuit || 310 A 40°C - 10 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Fire Resistance:
850°C IEC 60695-2-1
Maximum Operating Rate:
3600 cyc/h 60°C
Maximum Horse Power Rating:
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors
Width:
45 mm
Minimum Switching Current:
5 mA for Signaling circuit
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Net Weight:
0.54 kg
Overvoltage Category:
III
Circularity Profile:
ENVEOLI1102030EN
$241.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.