Schneider Electric

Schneider Electric LC1D806G7 IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D806G7
MPN:
LC1D806G7
Condition:
New
Climatic Withstand:
IACS E10 exposure to damp heat
Ip Degree Of Protection:
IP20 front face IEC 60529
Power Dissipation Per Pole:
5.1 W AC-3 || 12.5 W AC-1 || 5.1 W AC-3e
Minimum Switching Voltage:
17 V for Signaling circuit
Hold-In Power Consumption In Va:
26-26 VA 60 Hz cos phi 0.3 (at 20°C) || 26-26 VA 50 Hz cos phi 0.3 (at 20°C)
Rohs Exemption Information:
Yes
Pole Contact Composition:
3 NO
Pollution Degree:
3
Motor Power Kw:
22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 45 kW at 415...440 V AC 50/60 Hz (AC-3) || 55 kW at 500 V AC 50/60 Hz (AC-3) || 45 kW at 660...690 V AC 50/60 Hz (AC-3) || 15 kW at 400 V AC 50/60 Hz (AC-4) || 22 k
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Width:
85 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Depth:
130 mm
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Toxic Heavy Metal Free:
Yes
Coil Technology:
without built-in suppressor module
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Insulation Resistance:
> 10 MOhm for Signaling circuit
Warranty:
18 months
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: bars 1 - busbar cross section: 3 x 16 mm || power circuit: lugs-ring terminals - external diameter: 17 mm
Reach Regulation:
Free of Substances of Very High Concern above the threshold
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e <= 440 V
Country of Origin:
Czechia
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Environmental Disclosure:
ENVPEP110205EN
Operating Time:
20...35 ms closing || 6...20 ms opening
Mercury Free:
Yes
Mounting Support:
rail || plate
[Icw] Rated Short-Time Withstand Current:
640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Circularity Profile:
N/A
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Heat Dissipation:
6-10 W at 50/60 Hz
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
Mechanical Durability:
4 Mcycles
Minimum Switching Current:
5 mA for Signaling circuit
Range Of Product:
TeSys Deca
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Pvc Free:
Yes
Product Or Component Type:
contactor
Flame Retardance:
V1 conforming to UL 94
Signaling Circuit Frequency:
25...400 Hz
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Auxiliary Contact Composition:
1 NO + 1 NC
$363.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose