[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Compatibility Code:
LC1D
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Sustainable Packaging:
Yes
Circularity Profile:
N/A
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Operating Altitude:
0...9842.52 ft (0...3000 m)
Insulation Resistance:
> 10 MOhm for Signaling circuit
Mercury Free:
Yes
Signaling Circuit Frequency:
25...400 Hz
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Mounting Support:
rail || plate
Maximum Horse Power Rating:
7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Warranty:
18 months
Protective Cover:
with
[Uc] Control Circuit Voltage:
240 V AC 50/60 Hz
Fire Resistance:
850°C IEC 60695-2-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Maximum Operating Rate:
3600 cyc/h 60°C
Heat Dissipation:
6-10 W at 50/60 Hz
Climatic Withstand:
IACS E10 exposure to damp heat
Minimum Switching Current:
5 mA for Signaling circuit
Control Circuit Voltage Limits:
0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
Operating Time:
20...35 ms closing || 6...20 ms opening
Control Circuit Type:
AC 50/60 Hz
Weight:
1.61 kg
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Electrical Durability:
1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Width:
85 mm
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Environmental Disclosure:
ENVPEP110205EN
Rohs Exemption Information:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Free Of Svhc:
Yes
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Minimum Switching Voltage:
17 V for Signaling circuit
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Irms Rated Making Capacity:
1100 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Range:
TeSys
Pvc Free:
Yes
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Country of Origin:
Czechia
$437.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.