Schneider Electric

Schneider Electric LC1DT60AP7 IEC contactor, TeSys Deca, nonreversing, 60A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1DT60AP7
MPN:
LC1DT60AP7
Condition:
New
Contactor Application:
resistive load
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Pvc Free:
Yes
Control Circuit Type:
AC 50/60 Hz
Height:
122 mm
Mounting Support:
rail || plate
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Toxic Heavy Metal Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Depth:
120 mm
Net Weight:
1.09 kg
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
Range Of Product:
TeSys Deca
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Mechanical Durability:
6 Mcycles
Heat Dissipation:
4-5 W at 50/60 Hz
Reach Free Of Svhc:
Yes
Country of Origin:
Indonesia
Mercury Free:
Yes
Device Short Name:
LC1D
Overvoltage Category:
III
Signaling Circuit Frequency:
25...400 Hz
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Protective Treatment:
THIEC 60068-2-30
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Warranty:
18 months
Pollution Degree:
3
Poles Description:
4P
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Weight:
1.09 kg
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Coil Technology:
without built-in suppressor module
Environmental Disclosure:
ENVPEP1503009EN
Auxiliary Contact Composition:
1 NO + 1 NC
Electrical Durability:
1.4 Mcycles 60 A AC-1 <= 440 V
Eu Rohs Directive:
Compliant
Flame Retardance:
V1 conforming to UL 94
Range:
TeSys || TeSys Deca
Rohs Exemption Information:
Yes
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 60 A (at 60°C) for power circuit
Sustainable Offer Status:
Green Premium product
Circularity Profile:
ENVEOLI1503009EN
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Product Or Component Type:
contactor
Minimum Switching Voltage:
17 V for Signaling circuit
$353.16

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose