Schneider Electric

Schneider Electric LC1G2254BEEA Contactor, high power, TeSys Giga, advanced version, AC-1, <= 440V, 330A, 4 pole/NO, 24-48VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G2254BEEA
MPN:
LC1G2254BEEA
Condition:
New
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1
Inrush Power In Va:
290-290 VA
Hold-In Power Consumption In W:
5.7-5.7 W
Product Or Component Type:
contactor
Overvoltage Category:
III
Rated Breaking Capacity:
2050 A at 440 V
[Uc] Control Circuit Voltage:
24...48 V AC 50/60 Hz || 24...48 V DC
Weight:
5.1 kg
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Environmental Disclosure:
ENVPEP2105013
Country of Origin:
China
Coil Technology:
built-in bidirectional peak limiting
Connection Pitch:
35 mm
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Poles Description:
4P
Halogen Content Performance:
Halogen free plastic parts product
Net Weight:
5.1 kg
Operating Time:
40...70 ms closing || 15...50 ms opening
Ambient Air Temperature For Operation:
-25-60°C
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Color:
dark grey
Ambient Air Temperature For Storage:
-60-80°C
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Protective Treatment:
TH
Device Short Name:
LC1G
Circularity Profile:
ENVEOLI2105013
Auxiliary Contact Composition:
1 NO + 1 NC
Hold-In Power Consumption In Va:
10-10 VA
Contactor Application:
power switching
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Mounting Support:
plate
Rohs Exemption Information:
Yes
Power Dissipation Per Pole:
20 W AC-1 - Ith 330 A || 8 W AC-3 - Ith 225 A
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Associated Fuse Rating:
250 A aM at <= 440 V for motor || 200 A aM at <= 690 V for motor || 400 A gG at <= 690 V
Pole Contact Composition:
4 NO
Eu Rohs Directive:
Compliant with Exemptions
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Depth:
193 mm
Sustainable Offer Status:
Green Premium product
Tightening Torque:
18 N.m
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Inrush Power In W:
220 W
Pvc Free:
Yes
$1,730.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 330A @440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose