Schneider Electric LTMR100PFM Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240VAC
Schneider Electric
$850.00
Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240VAC
- Fire Resistance:
- 650°C EN/IEC 60695-2-12 || 960°C UL 94
- Current State 0 Guaranteed:
- logic input 0...40 V <= 15 mA 25 ms
- Ambient Air Temperature For Storage:
- -40-80°C
- Rohs Exemption Information:
- Yes
- Product Name:
- TeSys T
- Overvoltage Category:
- III
- Weight:
- 0.53 kg
- Connections - Terminals:
- control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
- Device Short Name:
- LTMR
- Compatibility Code:
- LTMR
- Logic Input Number:
- 6
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Product Or Component Type:
- motor controller
- Device Application:
- equipment monitoring and control
- Tightening Torque:
- control circuit 0.5-0.6 N.m flat 3 mm
- Measurement Accuracy:
- 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
- Sustainable Offer Status:
- Green Premium product
- Environmental Disclosure:
- ENVPEP060308EN_V2
- Web Services:
- web server
- Standards:
- EN 60947-4-1 || IACS E10 || CSA C22.2 No 14 || UL 508 || IEC 60947-4-1
- Load Current:
- 5 A 250 V AC logic output || 5 A 30 V DC logic output
- Current Consumption:
- 8...62.8 mA
- Electromagnetic Compatibility:
- electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 ||
- Product Certifications:
- KERI || RMRoS || ABS || UL || ATEX || NOM || RINA || BV || CCC || GL || DNV || CSA || LROS (Lloyds register of shipping) || EAC || C-tick
- Country of Origin:
- United States
- Protective Treatment:
- 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
- Metering Type:
- earth-fault current || phase current I1, I2, I3 RMS || temperature || imbalance current || average current Iavg
- Input Current:
- 3.1 mA 100 V || 7.5 mA 240 V
- Associated Fuse Rating:
- 4 A gG output || 0.5 A gG control circuit
- Communication Port Protocol:
- Profibus DP
- Depth:
- 122.5 mm
- Circularity Profile:
- ENVEOLI100411EN_V2
- [Us] Rated Supply Voltage:
- 100...240 V AC 50/60 Hz
- Connection Pitch:
- 5.08 mm
- Network And Machine Diagnosis Type:
- starting current and time || trip history information || running hours counter/operating time || phase fault and earth fault trip counters || trip context information || event recording || remaining operating time before overload tripping || motor co
- Ambient Air Temperature For Operation:
- -20-60°C
- Contacts Type And Composition:
- 1 NO + 1 NC fault signal || 3 NO
- Short-Circuit Withstand:
- 100 kA conforming to EN/IEC 60947-4-1
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- Pollution Degree:
- 3
- Bus Type:
- Profibus DP polarised 2-wire RS485 1...125 9.6 kbit/s...12 Mbit/s, SUB-D 9 2 shielded twisted pairs, type A || Profibus DP polarised 2-wire RS485 1...125 9.6 kbit/s...12 Mbit/s, terminal block 2 shielded twisted pairs, type A
- Halogen Content Performance:
- Halogen free plastic parts product
- [Ui] Rated Insulation Voltage:
- 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
- Permissible Power:
- 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
- Mechanical Robustness:
- vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
- Range:
- TeSys