Schneider Electric

Schneider Electric LTMR27EFM Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 outputs, 1.35 to 27A, 100 to 240 VAC

(No reviews yet) Write a Review
SKU:
LTMR27EFM
MPN:
LTMR27EFM
Condition:
New
Net Weight:
0.53 kg
Associated Fuse Rating:
4 A gG output || 0.5 A gG control circuit
Overvoltage Category:
III
Tightening Torque:
control circuit 0.5-0.6 N.m flat 3 mm
Web Services:
web server
Depth:
122.5 mm
Operating Altitude:
<= 6561.68 ft (2000 m) without derating
Permissible Power:
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Width:
91 mm
Current State 0 Guaranteed:
logic input 0...40 V <= 15 mA 25 ms
Metering Type:
average current Iavg || phase current I1, I2, I3 RMS || imbalance current || earth-fault current || temperature
Contacts Type And Composition:
1 NO + 1 NC fault signal || 3 NO
Measurement Current:
1.35-27 A
Fire Resistance:
650°C EN/IEC 60695-2-12 || 960°C UL 94
Mercury Free:
Yes
Input Current:
3.1 mA 100 V || 7.5 mA 240 V
[Uimp] Rated Impulse Withstand Voltage:
4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Standards:
IACS E10 || UL 508 || IEC 60947-4-1 || EN 60947-4-1 || CSA C22.2 No 14
Country of Origin:
Singapore
Mechanical Robustness:
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Compatibility Code:
LTMR
Protective Treatment:
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Device Short Name:
LTMR
Product Name:
TeSys T
Circularity Profile:
ENVEOLI100411EN_V2
Short-Circuit Withstand:
100 kA conforming to EN/IEC 60947-4-1
Network And Machine Diagnosis Type:
event recording || trip context information || phase fault and earth fault trip counters || trip history information || waiting time after overload tripping || fault recording || remaining operating time before overload tripping || starting current a
Product Certifications:
EAC || DNV || BV || C-tick || CCC || ABS || RINA || RMRoS || CSA || NOM || LROS (Lloyds register of shipping) || UL || KERI || GL || ATEX
Load Current:
5 A 250 V AC logic output || 5 A 30 V DC logic output
Product Or Component Type:
motor controller
Eu Rohs Directive:
Compliant with Exemptions
Rohs Exemption Information:
Yes
Ambient Air Temperature For Operation:
-20-60°C
Maximum Operating Frequency:
2 Hz
Communication Port Protocol:
Modbus TCP/EtherNet/IP
Bus Type:
Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
Protection Type:
phase unbalance || earth-leakage protection || thermal protection || reverse polarity protection || power factor variation || overload || load fluctuation || locked rotor || thermal overload protection || phase failure || overload (long time)
Warranty:
18 months
Sustainable Offer Status:
Green Premium product
[Us] Rated Supply Voltage:
100...240 V AC 50/60 Hz
Measurement Accuracy:
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Supply Voltage Limits:
93.5-264 V AC
Logic Input Number:
6
Range:
TeSys
Pollution Degree:
3
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Storage:
-40-80°C
$905.00

Description

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
View AllClose