- Suitability For Isolation:
- yes IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Ip Degree Of Protection:
- front cover IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -25-70°C
- Weight:
- 32 lb(US)
- Country of Origin:
- United States
- Circularity Profile:
- ENVEOLI2206033EN
- Range:
- PowerPact
- Mercury Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85°C
- Network Frequency:
- 50/60 Hz
- Local Signaling:
- overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
- Device Application:
- distribution
- Poles Description:
- 3P
- Wire Stripping Length:
- 30 mm
- Trip Unit Name:
- MicroLogic 5.0 A
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity Code:
- K
- Depth:
- 8.05 in
- Length:
- 30 mm
- Continuous Current Rating:
- 1
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount lug)
- Line Rated Current:
- 1200-1200 A
- Environmental Disclosure:
- ENVPEP2206033EN
- Warranty:
- 18 months
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.0 A, LSI
- Circuit Breaker Application:
- HACR rated
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Quantity Per Set:
- 1
- Terminal Identifier:
- AL1200P25K
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 50 kA 480 V AC 50/60 Hz UL 489 || AIR 50 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2