- Range Of Product:
- Preventa Safety automation
- Standards:
- IEC 61508 || IEC 61800-5-1 || ISO 13849-1 || IEC 62061
- Overvoltage Category:
- II
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV IEC 61800-5-1
- Number Of Outputs:
- 4 safety outputs OSSD safety outputs OSSD || 8 configurable diagnostic connection
- Number Of Inputs:
- 4 digital external device monitoring
- Product Or Component Type:
- safe output expansion module
- Electromagnetic Compatibility:
- electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 || electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields - test lev
- Electrical Connection:
- spring terminal
- Local Signaling:
- 1 LED green PWR power ON || 1 LED green RUN RUN (status) || 1 LED red E IN internal error || 1 LED red E EX external error || 2 LEDs orange ADDR node address || 4 LEDs green/red OUT output status || 4 LEDs yellow RST restart signal || 8 LEDs yellow S
- Ambient Air Temperature For Operation:
- -10-55°C
- Service Life:
- 20 year(s)
- Rohs Exemption Information:
- Yes
- Cable Cross Section:
- 0.2-2.5 mm² - AWG 24...AWG 14 flexible without cable end || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, without bezel || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, with bezel || 0.2-2.5 mm² - AWG 24...AWG 14 solid with ca
- Output Load:
- 60 Ohm
- Number Of Terminal Blocks:
- 6
- Ip Degree Of Protection:
- IP20 enclosure)
- Safety Reliability Data:
- DC > 99 % || MTTFd = 395 years high || PFHd = 8.64E-9 1/h
- [Us] Rated Supply Voltage:
- 24 V - 20...20 % DC
- Mounting Support:
- omega 35 mm DIN rail EN 50022
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Load Type:
- resistive load
- Discrete Output Voltage:
- 24 V DC
- Function Of Module:
- monitoring safety actuators discrete output || monitoring short-circuit and line break discrete output
- Discrete Output Current:
- 2 A || 100 mA
- Product Certifications:
- RCM || cULus || TÜV
- Country of Origin:
- Italy
- Mercury Free:
- Yes
- Connections - Terminals:
- 1 spring clamp terminals, removable terminal block || 2 spring clamp terminals, removable terminal block
- Insulation:
- 250 V AC between power supply and housing IEC 61800-5-1
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Vibration Resistance:
- +/-0.35 mm 10-55 Hz)IEC 61496-1
- Discrete Output Type:
- PNP
- Device Short Name:
- XPSMCM
- Discrete Input Voltage:
- 24 V DC
- Integrated Connection Type:
- backplane expansion bus
- Discrete Input Type:
- isolated
- Reach Free Of Svhc:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Power Consumption In W:
- 3 W
- Depth:
- 22.5 mm
- Pollution Degree:
- 2
- Relative Humidity:
- 10-95 %
- Net Weight:
- 0.25 kg
- China Rohs Regulation:
- X
- Safety Level:
- can reach category 4 ISO 13849-1 || can reach PL = e ISO 13849-1 || can reach SIL 3 IEC 61508 || SILCL 3 IEC 62061
- Ambient Air Temperature For Storage:
- -20-85°C